28

Remote controller wiring

• Strip approximately 14 mm of insulation off of the connecting wires.

• As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A

and B are reversed.

Wiring diagram

Wiring between indoor and outdoor units

NOTE

An outdoor unit that is
inter-connected to the
indoor units automatically
becomes the header unit.

Terminal block for remote controller
wiring of indoor unit

A
B

A
B

Remote controller wire (Field supply)

Terminal block

Remote
controller unit

Address setup

Set up the addresses as per the Installation Manual
supplied with the outdoor unit.

Wiring on the ceiling panel

As per the Installation Manual of the ceiling panel,
connect the connector (2P: Red) of the ceiling panel to
the connector (5P: White) onto the P.C. board within
the electric parts box.

6

ELECTRIC WORK

Connection of shield wire closed terminal

Control wiring between indoor and outdoor units

Control wiring between outdoor units

Outdoor power supply

Control wiring between indoor units

U2

U1

A B

B

A

Indoor unit

Earth

Remote

controller

Pull box

Earth leakage

breaker

Power switch

Indoor power supply
220-240V, 1N ~50Hz
220V, 1N ~60Hz

L N

U1 U2 U3 U4 U5 U6

Header outdoor unit

Earth

Outdoor power supply

U2

U1

A B

B

A

Indoor unit

Earth

Remote

controller

Pull box

L N

U2

U1

A B

B

A

Indoor unit

Earth

Remote controller

[Group control]

Pull box

L N

U2

U1

A B

Indoor unit

Earth

L N

U1 U2 U3 U4 U5 U6

Follower outdoor unit

Earth

Cord Clamp

5P connector (White)

Wire from ceiling panel

7

APPLICABLE CONTROLS

NOTIFICATION

When using the equipment for the first time, the remote controller will not accept any commands for a short
period of time.

• Automatic address

• While automatic addressing no operations can be performed on the remote controller.

• Automatic addressing will take a maximum duration of 10 minutes (generally 5 minutes).

• Upon turning on the unit after completion of automatic addressing, a maximum period of

10 minutes (generally 3 minutes) are required prior to the start up operation of the outdoor unit.

All indoor units are shipped from factory as standard. Change if necessary.

To change the setup use the main remote controller (wired remote controller).

* The setup change for wireless remote controller, sub remote controller or a unit without a controller (Centrally

controlled.) is not possible. In such cases, temporarily install a separate main remote controller.

Applicable control setup

Basic operation procedure for setup change

Change the setup while operation of the equipment is stopped.
(Be sure to stop the operation of a set.)

ON / OFF

FAN

TEMP.

SWING/FIX

TIME

MODE

VENT

UNIT

SET

CL

FILTER
RESET TEST

TIMER SET

CODE No.

UNIT No.

R.C.

No.

1

2

3

5

6

6

Procedure

1

2

3

4

5

6

Description

Push the

SET

,

CL

and

TEST

buttons simultaneously for 4 seconds or more, after a while, the display part flashes

as shown in the figure.
Check that the displayed item code is [10].
• If the item code indicates any characters other than [10], push the

TEST

button to erase the display and retry the operation from the first step.
(For some time after the

TEST

button has been pushed, the operation

of the remote controller cannot be accepted.)
(In a group control, the firstly displayed
indoor unit No. becomes the center unit.)

Each time the

UNIT

button is pushed, the indoor unit No. in the group control is displayed consecutively.

Select the indoor unit that requires a change to the setup.
During this time the indoor unit that is selected can be
confirmed as the louver and fan will be operated.

Using

TEMP.

the buttons, select the item code [

**

].

Using the

TIME

buttons, select set data [

****

].

Push the

SET

button. During this time, if the display changes from flashing to permanently on, the setup is

complete.
• To change the setup of an indoor unit that is not selected, restart operation from Procedure

2

.

• To change to a different setup within the selected indoor unit, restart operation from Procedure

3

.

Pushing the

CL

button clears the set up contents which has been set. In this case, restart from Procedure

2

.

When the setup is finished, push the

TEST

button. (The setup is configured.)

Pushing the

TEST

button deletes the display and returns the status to the

normal stopped status.
(For a period of time after the

TEST

button has been pushed, the remote

controller will not accept any commands.)

(* The display changes according

to the indoor unit model.)

CODE No.

UNIT No.

R.C.

No.

∗∗ ∗

∗∗

∗ ∗∗

CODE No.

UNIT No.

SETTING

R.C.

No.