Check code name

[P15]

Check code name

Gas leak detection

TD condition (Auxiliary code : 02)

Cause of operation

1. Outdoor unit service valve closed

2. Outdoor PMV error

3. TD sensor error

4. SV4 circuit error

5. Refrigerant shortage, clogging refrigerant

circuit

Coil, valve body, coil installation,
disconnection of cable, etc.

Open service valves fully.

Repair outdoor PMV.

Replace TD1 or TD2 sensor.

Repair SV41 and SV42 circuits.

Correct cabling.

Are service valves of gas

and liquid sides fully opened?

Are characteristics of

TD1, TD2 sensor resistance normal?

Is SV4 valve circuit normal?

(Coil misinstallation, valve leakage)

Are not indoor units in different

refrigerant circuit connected?

Refrigerant shortage,

clogging, pipe breakage.

Connectors CN300, 301 White

Refer to outdoor unit temperature
sensor characteristics-4.

Check with miscabling check
function of outdoor unit.

(Check there is no clogging and pipe breakage, and then recharge refrigerant.)

Is outdoor PMV1, 2 normal?

1. Connector connection
2. Cabling
3. Coil
4. Valve body
5. Outdoor I/F P.C. board

( )

( )

YES

NO

YES

YES

YES

YES

NO

Replace defective parts.

Check leakage of

SV5 and SV11 circuits.

Normal

Abnormal

Correct piping.

Check mispiping of discharge gas/

suction gas main pipes.

Normal

Normal

Abnormal

Repair the flow selector unit.

Abnormal

NO

NO

NO

Is the flow selector unit normal?

Check code name

[P17]

Check code name

Discharge temp TD2 error

Cause of operation

1. Outdoor unit service valve closed

2. Outdoor PMV error

3. TD sensor error

4. Refrigerant shortage, clogging of refrigerant circuit

5. 4-way valve error

6. SV4 circuit leakage, misinstallation

7. SV5 circuit leakage

8. SV6 circuit clogging

9. Mispiping of discharge gas/suction gas pipes

10. Flow selector unit error

Open service valves fully.

Repair outdoor PMV.

Replace TD2 sensor.

Check 4-way valve.

Correct cabling.

Are service valves of gas and

liquid sides fully opened?

Are characteristics of

TD2 sensor resistance normal?

Refrigerant shortage, clogging, pipe breakage.

* Connectors CN300, 301 White

* Refer to outdoor unit

temperature sensor
characteristics-4.

(Check there is no pipe breakage, and then recharge refrigerant.)

Is outdoor PMV normal?

1. Connector connection
2. Cabling
3. Coil
4. Valve body
5. Outdoor I/F P.C. board

SV4 circuit

1. Are not SV41 and SV42 valve

coils installed reversely?

2. Is there no leakage through

SV42 circuit?

YES

NO

NO

YES

YES

YES

YES

NO

NO

NO

Is not an indoor unit of different

refrigerant line connected?

YES

NO

Correct piping.

YES

YES

YES

YES

Check mispiping of discharge gas/

suction gas main pipes.

Does not discharge refrigerant gas by

pass to suction sidethrough 4-way valve?

NO

Replace defective parts.

NO

Replace defective parts.

NO

Repair the flow selector unit.

NO

Correct installation of valve coil.

Replace SV42 valve.

Check with miscabling check
function of outdoor unit.

( )

Check leakage of SV5 circuit.

Check clogging of SV6 circuit.

Is the flow selector unit normal?