Check code

[E06]

Check code name

Decreased number of indoor units

Cause of operation

1. Communication lines (U1, U2) connection

error between indoor and outdoor

2. Connector connection error of communica-

tion for indoor P.C. board

3. Connector connection error of communica-

tion for outdoor I/F board

4. Power supply of indoor unit

(Is power turned on?)

Auxiliary code : No. of indoor units which received signals normally

(NOTE)
1. When signal is not sent for a certain period from the indoor unit

which has used to send signals normally, [E06] is displayed.

Is power of indoor turned on?

Did a power failure occur?

Is there no noise, etc?

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Is there no miscabling/

disconnection on communication line

betweenindoor and outdoor?

Is connection of CN40 connector

on indoor P.C. board normal?

Is connection of CN01 connector

on outdoor I/F P.C. board normal?

Check indoor P.C. board.

Defect

Replace

Check noise, etc, and eliminate it if any.

Clear the check code.

Turn on power of indoor unit.

Correct cabling of cable connector.

Correct communication line.

Check code

[E07]

Check code name

Indoor/Outdoor

communication circuit error

(Detected at outdoor side)

Cause of operation

1. Indoor/outdoor communication end terminal

resistance setup error

2. Indoor/outdoor communication connection

error

Is there noise source?

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Is setup of end terminal resistance

of outdoor unit normal?

Is inter-unit cable (U1, U2) between

indoor and outdoor short-circuited?

Is connection of inter-unit wire

between indoor and outdoor correct?

Is there no error on

power wire to outdoor unit?

Is F400 (fuse) on

I/F P.C. board opened?

Outdoor I/F P.C. board failure

Replace

Eliminate noise.

Correct power wire.

Correct

communication line.

I/F P.C. board failure
However an emergent operation is
available by inserting connector to
be connected to CN01 to CN33.

Correct short-circuit.

* Check conduction

with tester.

Turn on power to
start operation.

Correct setup of end
terminal resistance.