Is there group cabling?

Check indoor P.C. board.

Failure

®

Replace

There is individual indoor unit.

Correct indoor group address.

Check setup item code

DN 12, 13, and 14 addresses.

Item code (D1) 12: Line address
Item code (D2) 13: Indoor address
Item code (D3) 14: Group address

YES

YES

NO

NO

Check code name

[L07]

Check code name

Group line in individual indoor unit

Cause of operation

The group line is connected in the
individual indoor unit.

Turn on the power of indoor units.

Turn on the power of outdoor unit again.

Are powers of all the

indoor units turned on?

Disconnect connectors between

[U1, U2] and [U3, U4].

Clear addresses.

(Refer to “Address clear”.)

Re-execute address setup.
(Refer to “Address setup”.)

YES

NO

Check code name

[L08]

Check code name

Indoor group / address unset

Cause of operation

Indoor address unset

Note) This code is displayed when the power is turned on at the first time after installation.

(Because the address is not yet set up)

Set up capacity data of indoor unit.

(Setup item code (DN) = 11)

Check indoor P.C. board.

Defect

Replace

Are capacity setups

of indoor units unset?

YES

NO

Check code name

[L10]

Check code name

Outdoor capacity unset

Cause of operation

On the outdoor IF P.C. board for service, the
model selecting jumper has not been set up so
as to match with the model.

I/F P.C. board A’ssy service for the outdoor unit is common to this series. A setup for model selection different from
that for P.C. board with trouble is necessary. Set up a model based upon the P.C. board A’ssy exchange procedure.

Check code name

[L09]

Check code name

Indoor capacity unset

Cause of operation

Indoor capacity unset

Check code name

[L17]

Check code name

Inconsistent models of

outdoor units

Cause of operation

There are outdoor units on the communication
line other than Super Module Multi Flex type
such as Super Module Multi or Super Module
Multi ice regenerative type

Using 7-segment on I/F P.C. board, check the model name for each outdoor unit.
For check, when putting the rotary switch on SW01/02/03=16/16/16, it is an
outdoor I/F P.C. board for Super Module Multi Flex if “F” is displayed at the left
side of 7-segment [A] part.

Is the check code [L17]

displayed even if turning on again

power of all the connected outdoor

units on 1 system alone?

Are all the connected

outdoor I/F P.C. boards on 1 system

P.C. boards of outdoor units for

Super Module Multi Flex?

Check again whether there is any
other outdoor unit or not on the
communication line in 1 system.
If any, turn off power of the
corresponding outdoor unit and
then check once more.

Replace outdoor units of other models
with outdoor units purposed for flex.

Correct communication line between
outdoor units.

Change the incorrectly built-in outdoor
I/F P.C. boards with I/F boards for
Super Module Multi Flex.

Are the connected outdoor

units those for flex on 1 system?

(Check model name.)

YES

YES

YES

NO

NO

NO