41

TYPE

Item code [10]

Indoor unit capacity

Item code [11]

Type

Compact 4-way Air Discharge Cassette

Abbreviated
Model name

MMU-AP XXX MH

Setup data

0001

0003

0005

0007

0009

Model

007

009

012

015

018

Setup

data

0014

6-2. Applied Control in Indoor Unit

n

Remote location ON/OFF control box (TCB-IFCB-4E)

[Wiring and setup]

• Use the exclusive connector for connection with the indoor control P.C. board.

• In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in the

group. However when taking out the operation/error signal from the other unit, it is necessary to take out from
each unit individually.

(1) Control items

1) Start/Stop input signal : Operation start/stop in unit

2) Operation signal

: Output during normal operation

3) Error signal

: Output during alarm

(Serial communication error or indoor/outdoor protective device) operation

(2) Wiring diagram using remote control interface (TCB-IFCB-4E)

Input

IFCB-4E : No voltage ON/OFF serial signal

Output

No voltage contact for operation, error display

Contact capacity: Below Max. AC240V 0.5A

1
2
3
4
5
6

CN61

T10

(YEL)

1
2
3
4

1
2
3
4

5
6

CN13

CN06

Start/Stop input

ON/OFF serial
signal input

Indoor control P.C. board

Remote location ON/OFF control box

(TCB-IFCB-4E)

COM (GND)

Remote controller prohibition/clear input

Operation signal output

COM (+12V)

Error signal output

COM

Operation signal output

Error signal output

Power supply 220–240V,

~

50Hz