Is backup operation of outdoor unit being set up?

Is No. of connected indoor units correct?

Is setup of indoor unit HP correct?

Is total capacity of connected

indoor units within 135%? ( 1)

For a service P.C. board, check outdoor HP setup.

(Set up jumper 9, 10, 11, and 12.)

Set up outdoor HP.

(Refer “How to exchange interface P.C. board”.)

Set capacity of connected

indoor units within 135% of outdoor units.

Correct HP setup.

Excessive indoor units are connected.

Correct miswiring.

Perform setup of no detection

for capacity over.

Check outdoor interface P.C. board A’ssy.

Check code

[E16]

Check code name

Connected indoor units

capacity over

Cause of operation

1. There are 48 or more connected indoor units.

2. Capacity over of total connected indoor units.

3. Incorrect setup of indoor/outdoor capacity

Auxiliary code : 00 : Capacity over 01 : ~ : Number of connected indoor units

(

∗∗∗∗∗

1) When capacity of the outdoor unit is 12HP,

up to the maximum capacity 120% of
indoor units can be connected.

YES

YES

YES

YES

NO

NO

NO

NO

Is a group control operation?

Check indoor address.

Correct indoor address.

Is there any disconnection of

connector or wiring from terminal block

of indoor unit?

Are remote controller

inter-unit wires (A/B) normal?

Are powers of

all indoor units turned on?

Check indoor P.C. board.

Failure

Replace

Check power connection status

of indoor unit.

Correct connection of connector.

Check circuit wire.

Correct remote controller

inter-unit wire.

Check code

[E18]

Check code name

Communication error between

indoor header and follower

Cause of operation

Regular communication between indoor header
and follower is unavailable.

YES

YES

NO

NO

Are not communication lines (U1, U2)

between indoor and outdoor connected

to multiple outdoor units?

Is communication line between indoor and

outdoor connected to one unit per 1 system?

Check I/F board.

Connect communication line between indoor
and outdoor.

Connect communication line between indoor
and outdoor to one unit per 1 system.

Check code

[E19]

Check code name

Header outdoor units quantity error

Cause of operation

1. Misconnection of inter-unit cable between

indoor and outdoor

2. Outdoor I/F P.C. board error

Auxiliary code : 00: No header unit 02: Two or more header units

Reference)
When the power supply of the outdoor unit is firstly
turned on, the check code [E19 00] is displayed until the
power supplies of the indoor units are turned on. However
it is not an error. If the power supplies of the indoor units
are turned on, the check code is automatically reset.