2. Data display of outdoor unit information (Displayed on each outdoor unit)

SW01

1

SW02

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

SW03

1

Display contents

Error data

A

Displays outdoor unit number: [U1] to [U4]

B

Displays check code (Latest code only is displayed.)

There is no check code: [– – –]

There is auxiliary code: Check code [

] for 3 seconds,

auxiliary code [–

] for 1 second alternately

<SW04> push function

: Fan of unit with error only drives. 7-segment A: [E1]

<SW04 + SW05> push function : Fan of normal unit only drives. 7-segment A: [E0]
<SW05> push function

: Interruption of fan operation function

A

B

Operation mode

A

Stop: [ ]
Normal cooling: [ C], Normal heating: [ H], Normal defrost: [ J]

B

Outdoor unit HP

A

5HP: [ 5], 6HP: [ 6], 8HP: [ 8], 10HP: [10], 12HP: [12]

B

[HP]

Compressor operation command

A

No.1 compressor operation command is displayed.
Data display with Hexadecimal notation: [00 to FF]

B

No.2 compressor operation command is displayed.
Data display with Hexadecimal notation: [00 to FF]

<SW04> push function

: Inverter frequency is exchanged to decimal notation.

7-segment display (A/B)

: [

] [

H] (Normal display by pushing <SW05>)

Outdoor fan step

A

[FP]

B

Step 0 to 31: [ 0 to 31]

Compressor backup

A

Displays No.1 compressor setup status
Normal: [ ], Backup setup: [C1]

B

Displays No.2 compressor setup status
Normal: [ ], Backup setup: [C2]

A

B

Control valve output data

Displays control output status of solenoid valve

A

B

4-way valve: ON

H. 1

… … …

4-way valve: OFF

H. 0

… … …

SV2: ON / SV5: OFF

2. 1

… 5. 0

SV2: OFF / SV5: ON

2. 0

… 5. 1

SV3A: ON / SV3B: OFF / SV3C: OFF /SV3D: OFF

3. 1

0 0 0

SV3A: OFF / SV3B: ON / SV3C: OFF /SV3D: OFF

3. 0

1 0 0

SV3A: OFF / SV3B: OFF / SV3C: ON /SV3D: OFF

3. 0

0 1 0

SV3A: OFF / SV3B: OFF / SV3C: OFF /SV3D: ON

3. 0

0 0 1

SV41: ON / SV42: OFF

4. …

1 0 …

SV41: OFF / SV42: ON

4. …

0 1 …

… …

… … …

… …

… … …

PMV1 /PMV2 opening

Displays opening data (Decimal) (Total opening)

. P

. P

Oil level judgment status

A

[oL]
<SW05> push SW function: The following data is displayed for 2 seconds.
* During oil shortage in compressor 1: [L …],

during oil shortage in compressor 2: [… L]

B

Initial display: [… … …], Oil level judgment result: [A. #.

]

Judgment result of compressor 1 in [#], compressor 2 in [

]

(0: Normal, 1, 2: Shortage) is displayed.