Toshiba MMU-AP0121MH User Manual

Page 70

Advertising
background image

70

Auxiliary code

01

02

03

04

05

06

07

P.C. board to be replaced

IPDU1

IPDU2

IPDU1, 2

Fan IPDU

IPDU1, fan IPDU

IPDU2, fan IPDU

IPDU1, 2, fan IPDU, I/F

Is jumper lead setup of the outdoor I/F P.C. board correct?

(Jumper 7, 8, 9 ON)

NO

NO

YES

YES

YES

YES

YES

NO

NO

NO

NO

YES

Connect the jumper lead.

Correct connection of connectors.

Replace communication line.

I/F P.C. board error

IPDU P.C. board error

Replace fan power supply P.C. board.

Are communication connectors

between I/F, fan power supply board,

and IPDU connected?

Is there voltage deflection between

4 and 5 pins of CN600 on I/F P.C. board?

(Measurement with tester: DC 0 to 5V, 5 pin GND)

Is there voltage deflection between

3 and 5 pins of CN600 on I/F P.C. board?

(Measurement with tester: DC 0 to 5V, 5 pin GND)

On the fan power supply P.C. board,

1) CN503: Between 1 and 5 pins

12V

2) CN503: Between 2 and 5 pins

7V

3) Between +5V and GND at the side of CN505: 5V

Replace P.C. board according to auxiliary code.

When IPDU (No.1, No.2) and
three fan IPDU do not return communication

Is there no disconnection of communication line
between I/F, fan power supply board, and IPDU?

Check code

[E31]

Check code name

IPDU communication error

Cause of operation

1. Connection error of communication line

between IPDU and I/F P.C. board

2. I/F P.C. board error

3. IPDU P.C. board error

4. External noise

Auxiliary code :
01: IPDU1 error

02: IPDU2 error

03: IPDU1, 2 error

04: Fan IPDU error

05: IPDU1, fan IPDU error

06: IPDU2, fan IPDU error

07: All IPDU error or communication line error between IPDU-I/F P.C. boards, or outdoor I/F P.C. board error

If the fan IPDU is abnormal, be sure to check the voltage output on the fan power supply P.C. board.

Check code

[F01]

Check code name

Indoor TCJ sensor error

Cause of operation

TCJ sensor Open/Short

Check code

[F03]

Check code name

Indoor TC1 sensor error

Cause of operation

TC1 sensor Open/Short

Check code

[F02]

Check code name

Indoor TC2 sensor error

Cause of operation

TC2 sensor Open/Short

Correct connection of connector.

Replace TC2 sensor.

Is TC2 sensor connector (CN101: Black)

on indoor P.C. board normally connected?

Are characteristics of TC2 sensor

resistance value normal?

Check indoor main P.C. board.

Defect

Replace

YES

YES

NO

NO

Indoor unit temperature sensor characteristics
See Characteristics-2.

YES

YES

NO

NO

Correct connection of connector.

Replace TCJ sensor.

Is TCJ sensor connector (CN102: Red)

on indoor P.C. board normally connected?

Are characteristics of TCJ sensor

resistance value normal?

Check indoor main P.C. board.

Defect

Replace

Indoor unit temperature sensor characteristics
See Characteristics-2.

YES

YES

NO

NO

Correct connection of connector.

Replace TC1 sensor.

Is TC1 sensor connector (CN100: Brown)

on indoor P.C. board normally connected?

Are characteristics of TC1 sensor

resistance value normal?

Check indoor main P.C. board.

Defect

Replace

Indoor unit temperature sensor characteristics
See Characteristics-2.