Cause of operation

Outside error was input.

Does outside device correctly operate?

Check cause of the operation.

Is outside device connected

to connector CN80?

Check indoor P.C. board.

Failure

Replace

Check outside device.

Failure

Replace

YES

YES

NO

NO

Check outdoor I/F P.C. board.

Is there any trouble of

outdoor unit power supply?

Check power voltage and line.
Check auxiliaty noise, etc.

NO

YES

Is not there mechanical lock of fan motor?

Is there no connection error or

disconnection of CN076 connector?

Correct cabling circuit for

the connector connection.

Check indoor P.C. board.

Failure

Replace

Replace fan motor.

YES

YES

NO

NO

Check code name

[L30]

Check code name

Interlock in indoor unit

from outside

Check code name

[P01]

Check code name

Indoor fan motor error

Cause of operation

1. Cabling error

2. Check fan motor.

* For the models installed with AC fan motor only

Check code name

[L31]

Check code name

Extended IC error

Cause of operation

1. Outdoor unit power error

2. Outdoor I/F P.C. board error

Check code name

[P03]

Check code name

Discharge temp TD1 error

Cause of operation

1. Service valve of outdoor unit closed.

2. Outdoor PMV1, 2 error

3. TD sensor error

4. Refrigerant short, clogging in pipe

5. 4-way valve error

6. SV4 circuit leakage, misinstallation

7. SV5 circuit leakage

8. SV6 circuit clogging

9. Discharge gas/Suction gas pipes mispiping

10. Flow selector unit error

Are service valves of

outdoor discharge gas, suction gas,

and liquid pipe fully opened?

* Connector CN300, 301 White

(Check there is no pipe breakage, and then recharge refrigerant.)

Is resistance characteristic

of TD1 sensor normal?

Is not indoor unit in other

refrigerant line connected?

Check mispiping of discharge gas /

suction gas main pipes.

Is there no refrigerant leakage of

discharge gas to suction side in 4-way valve?

Refer to Outdoor unit temperature
sensor characteristics-4.

YES

YES

YES

YES

YES

Normal

Normal

Normal

YES

YES

NO

NO

NO

NO

NO

Abnormal

Abnormal

Abnormal

NO

NO

Are outdoor PMV1 and PMV2 normal?

1. Connector connection
2. Wiring
3. Coil
4. Valve itself
5. Outdoor P.C. board

SV4 circuit

1. Are not coils of SV41 and

SV42 valves mounted reversely?

2. Is no leakage from SV41?

Check leakage of SV5 circuit.

Is the flow selector unit normal?

Check clogging of SV6 circuit.

Refrigerant short, clogging, pipe breakage

Open service valves fully.

Repair outdoor PMV.

Replace TD1.

Check 4-way valve.

Correct mounting of valve coils

or replace SV41 valve.

Replace defective parts.

Replace defective parts.

Correct piping.

Repair flow selector unit.

Correct wiring.