Toshiba MMU-AP0121MH User Manual

Page 87

Advertising
background image

87

All heating operation

Is indoor PMV normal?

Is SV5 circuit normal?

Is there a clogging?

Check and correct cabling.

Repair SV5 circuit.

Replace PMV body

.

Repair faulty parts.

Replace TC2 or TCJ sensor.

Repair faulty parts.

Eliminate the interfered causes.

Refrigerant overcharge,

clogging, pipe breakage,

abnormal overload condition

Is connector

connection of indoor

heat exchanger fan or

fan motor normal?

Are characteristics

of sensor TC2 and TCJ

resistance normal?

Is connector connection

coil normal?

Does heating indoor fan

normally operate?

Is check valve of main

discharge pipe normal?

Are not indoor units of different

refrigerant circuit connected?

Check indoor P.C. board.

Faulty

Replace

C

Is there a cause to

interfere operation of

heat exchanger of indoor unit?

1. Air filter clogging
2. Heat exchanger clogging
3. Air short circuit

Coil error, choke,

disconnection of cable, etc.

( )

( )

Check with miscabling check function
of outdoor unit.

Repair check valve.

Replace

Repair check valve.

Replace

YES

YES

YES

YES

NO

NO

Check operation of 4-way valve.

Replace 4-way valve.

Normal

Abnormal

Check clogging of SV11 circuit.

Replace defective parts.

Normal

Abnormal

NO

NO

YES

YES

YES

YES

YES

NO

NO

NO

YES

NO

NO

NO

Check code name

[P22]

Check code name

Outdoor fan IPDU error

Cause of operation

1. Fan lock

2. Fan IPDU P.C. board error

3. Overload cause

4. External cause such as blast

5. Fan IPDU power P.C. board error

Auxiliary code:

0

: IGBT short circuit

1

: Position detect circuit error

3

: Motor lock error

4

: Motor current error detected

C

: TH sensor error (Heat sink overheat)

D

: TH sensor error

E

: Vdc error

Is not outdoor fan motor locked?

Is sub-code of outdoor I/F P.C. board [0d]?

Check fan IPDU.

Correct cable connector connection.

Correct cause of overload.

Retightening of screws, etc.

Replace fan IPDU.

Is there no problem

such as stuffing or blast blowing to

discharge port of outdoor fan?

Are wire connector

connection on fan IPDU and

power P.C. board A’ssy normal?

Is there no loosening on fixation

between fan IPDU and heat sink?

Replace motor.

YES

YES

YES

YES

YES

Is winding resistance of the motor correct?

13 to 33 (Between R and S, R and T, S and T)

YES

NO

YES

NO

NO

NO

NO