Check code

Main

remote

controller

P22

P26

P29

P31

Outdoor 7-segment display

Check code

P22

P26

P29

Auxiliary code

0: IGBT shortage

1: Position detection circuit error

3: Motor lock error

4: Motor current error detection

C: TH sensor temp. error

D: TH sensor error

E: Vdc error

01: Compressor 1 side

02: Compressor 2 side

01: Compressor 1 side

02: Compressor 2 side

Detected

position

FAN-IPDU

IPDU

IPDU

Indoor

Check code name

Outdoor fan IPDU error

G-Tr short-circuit
protection error

Compressor position
detection circuit error

Other indoor error
(Group follower unit error)

Status

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

Corresponding

unit only stops.

Error detection condition

(Auxiliary code: 0)

• Short-circuit current was detected at start time.

• Short-circuit current was detected when

checking IGBT short-circuit before start time.

(Auxiliary code: 1)

• The standard value of detection circuit of fan

IPDU current fluctuated at start time.

(Auxiliary code: 3)

• Abnormal current was detected within 30

seconds after start time.

(Auxiliary code: 4)

• Short-circuit current was detected when

2 seconds or more passed after start time.

• Over-current was detected when 30 seconds

or more passed after start time.

(Auxiliary code: C)

• Heat sink sensor (TH) of fan IPDU detected

95°C error.

(Auxiliary code: D)

• Heat sink sensor (TH) of fan IPDU detected

short-circuiting or open.

(Auxiliary code: E)

• Input power supply voltage of the fan IPDU

over the setup value was detected.

• Input power supply terminal of the fan IPDU

was unconnected.

• Power supply P.C. board error of the fan IPDU

Instantaneous over-current was detected when
compressor started.

Position was not normally detected.

E07/L07/L03/L08 was detected when other
indoor unit in the group was defective.

Check item (position)

• Check fan motor. (Interphase short-circuit)

• Check fan IPDU error.

• Check fan IPDU error.

• Check fan motor. (Lock, phase missing)

• Check cause of abnormal overload at start time.

• Check connection of connector to fan motor.

• Check power supply voltage.

• Check fan IPDU error.

• Check outdoor fan system.

• Check fan IPDU error.

• Check fixation between fan IPDU and heat sink.

• Check fan IPDU error.

• Check input power supply voltage of the fan IPDU.

• Check power supply P.C. board error of the fan IPDU.

• Check error of external electrolytic condenser.

• Check connector connection and wiring on IPDU P.C. board.

• Check compressor error and defect of compressor coil.

• Check outdoor P.C. board (IPDU) error.

• Check connector connection and wiring.

• Check compressor error and defect of compressor coil.

• Check P.C. board (IPDU) error.

• Check indoor P.C. board.