Toshiba MMU-AP0121MH User Manual

Page 58

Advertising
background image

58

Check code

Main

remote

controller

L06

L07

L08

L09

L10

L17

L18

L20

L28

L29

L30

Outdoor 7-segment display

Check code

L06

L08

L10

L17

L18

L28

L29

L30

L31

Auxiliary code

No. of indoor units with priority

Corresponding indoor address

01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 errors
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error or communication

error between IPDU and I/F P.C.
board, or outdoor I/F P.C. board error

Detected indoor address

Detected

position

I/F

Indoor

Indoor

Indoor

I/F

I/F

I/F

Indoor

I/F

I/F

Indoor

I/F

Check code name

Duplicated indoor units with priority
(Displayed on the unit other than
indoor unit with priority)

Group line in individual indoor unit.

Indoor group / address unset

Indoor capacity unset

Outdoor capacity unset

Inconsistent models of outdoor
units

FS unit system error

Duplicated central control
addresses

Quantity over of connected outdoor
units

IPDU quantity error

Interlock in indoor unit from outside

Extended IC (Integrated Circuit)
error

Status

All stop

Corresponding
unit only stops.

Corresponding
unit only stops.

Corresponding
unit only stops.

All stop

Corresponding
unit only stops.

All stop

All stop

All stop

Corresponding
unit only stops.

Operation

continues.

Error detection condition

Indoor units with priority were
duplicated.

At least one indoor unit connected
to a group existed in the individual
indoor units.

Address was not yet set up.

Indoor unit capacity was unset.

On the I/F P.C. board for service,
jumper line was not cut according to
the model.

Outdoor units of 1 series and those
of 2 series were mixed.

An indoor unit which is not
connected with FS unit is driving
without setup for cooling only mode.

Duplicated central control
addresses

There were more than four outdoor
units.

No. of IPDU units detected when
power was turned on were less.

• Outside error input terminal

Detected signal to (CN80) for
more 1 minute

P.C. board (I/F) parts error

Check item (position)

• Check display of indoor unit with priority and outdoor unit.

• Check indoor address.

• Check indoor address.

Note)
After installation, this code is displayed when the power is firstly
turned on.

Set up indoor capacity. (DN=11)

Check model setup on outdoor I/F P.C. board A’ssy for service.

• Check outdoor units.

• Check setup of remote controller (DN=[OFF]).
• Check FS unit.

Check pipe connection to FS unit.
(Mispiping between discharge gas and suction gas)
Check miswiring/misinstallation of SVS/SVD valves.

• Check central control address.
• Check network adaptor P.C. board. (In case of AI-NET)

• Check No. of connected outdoor units.

(Max. 4 units per 1 system)

• Check communication line between outdoor units.
• Check outdoor P.C. board (I/F) error.

• Check model setup for outdoor I/F service P.C. board.
• Check connection of UART communication connector.
• Check IPDU, fan IPDU, and I/F P.C. board error.

Note)
UART: Universal Asynchronous Receiver Transmitter

n

Outside device is connected to connector (CN80):
1) Check outside device error.
2) Check indoor P.C. board error.

n

Outside device is not connected to connector (CN80):
1) Check indoor P.C. board error.

Check indoor (I/F) P.C. board.

Check indoor (I/F) P.C. board.