Toshiba MMU-AP0121MH User Manual

Page 84

Advertising
background image

84

Check code name

[P13]

Check code name

Outdoor liquid back detection error

Cause of operation

1. PMV1/PMV2 error

2. Pd sensor, Ps sensor error

3. Clogging of SV2 circuit

4. Clogging of SV3B circuit, balance pipe

5. Leakage of main discharge pipe

6. Outdoor I/F P.C. board error

Check I/F P.C. board.

Is SV2 valve coil correctly connected?

Is there no miswiring or

misinstallation on TS1 and TS2 sensors?

Are connections of outdoor

PMV1/PMV2 connectors correct?

Are operations of outdoor

PMV1/PMV2 normal?

Are characteristics of Pd sensor/Ps sensor

output voltage normal?

PMV error

Pd sensor/Ps sensor error

Correct connector connection.

(CV2: CN302)

Correct connector connection.

(CN300, CN301)

Correct miswiring/installation

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

Check code name

[P15]

Check code name

Gas leak detection

TS condition (Auxiliary code : 01)

Cause of operation

1. Outdoor unit service valve closed

2. Outdoor PMV error

3. TS1 sensor error

4. Refrigerant shortage, clogging refrigerant

circuit

5. 4-way valve error

6. SV4 circuit error

( )

Open service valves fully.

Repair outdoor PMV.

Replace TS2 sensor.

Check and replace 4-way valve and coil.

Repair SV41 and SV42 circuits.

Are service valves at gas and

liquid side fully opened?

Are characteristics of

TS2 sensor resistance normal?

Is there no leakage of

SV41 and 42 valve circuits?

Refrigerant shortage,

clogging, pipe breakage.

Connectors CN300, 301 White

Refer to outdoor unit temperature
sensor characteristics-3.

(Check there is no clogging and pipe breakage, and then recharge refrigerant.)

Coil, valve body,
disconnection of cable, etc

Is outdoor PMV1, 2 normal?

1. Connector connection
2. Wiring
3. Coil
4. Valve body
5. Outdoor I/F P.C. board

Normal

Normal

YES

YES

YES

YES

NO

NO

Correct piping.

Check mispiping of discharge gas/

suction gas main pipes.

YES

Abnormal

Repair the flow selector unit.

Abnormal

NO

NO

NO

Does not discharge

refrigerant gas bypass to suction side

through 4-way valve?

Is the flow selector unit normal?