Toshiba MMU-AP0121MH User Manual

Page 52

Advertising
background image

52

Check code

Main

remote

controller

E12

E15

E16

E18

E19

E20

E23

E25

E26

E28

Outdoor 7-segment display

Check code

E12

E15

E16

E19

E20

E23

E25

E26

E28

Auxiliary code

01: Indoor/outdoor communication
02: Between outdoors communication

00: Capacity over
01 to: No. of connected units

00: No header unit
02: Two or more header units

01: Connection of outdoor of other line
02: Connection of indoor of other line

No. of normally received outdoor units

No. of detected outdoor units

Detected

position

I/F

I/F

I/F

Indoor

unit

I/F

I/F

I/F

I/F

I/F

I/F

Check code name

Automatic address
start error

No corresponding
indoor unit during
automatic address

No. of connected
indoor units /
Capacity over

Communication error
between indoor header
and follower units

Outdoor unit quantity
error

Other line unit
connected during
automatic address

Communication
sending error between
outdoor units

Duplicated outdoor
follower address setup

Decreased number of
connected outdoor
units

Outdoor follower unit
error

Status

All stop

All stop

All stop

Corresponding
unit only stops.

All stop

All stop

All stop

All stop

All stop

All stop

Error detection condition

• When indoor automatic address started,

other refrigerant circuit system was setting
automatic address.

• When outdoor automatic address started,

indoor automatic address was executed.

Indoor unit is not found when indoor automatic
address start was set up.

• Total capacity of indoor units exceeded

135% of total outdoor capacity.

• No. of connected indoor units are more than

48 units.

[Note]
If this code appears after backup setup of
outdoor unit trouble, set up “No. capacity-over
detection”.
<Setup method of “No. capacity-over
detection”>
Turn on SW09/Bit 2 on I/F P.C. board of
outdoor header unit.

Regular communication between indoor
header and follower units

• There are multiple outdoor units in 1 line.
• There is none of outdoor unit in 1 line.

Unit of other line was connected when indoor
automatic address started.

Transmission of other outdoor unit was
unavailable for 30 seconds or more.

Outdoor addresses manually set up are
duplicated.

The signal was not returned for constant from
the outdoor unit which was receiving signal.

Outdoor header unit received error code from
outdoor follower unit.

Check item (position)

• Setup the address again after disconnecting communication

connection with other refrigerant circuit system.

• Check the communication line connection between indoor and outdoor.
• Check the electric power line error in indoor.
• Check the noise of surrounding devices.
• Power failure
• Check indoor P.C. board error.

• Check the connection capacity of indoor unit.
• Check the HP capacity of indoor unit.
• Check the indoor/outdoor capacity setup
• Check the No. of connected indoor units.
• Check the outdoor I/F P.C. board error

• Check cable of the remote controller.
• Check power cabling of indoor.
• Check P.C. board of indoor.

The outdoor unit connected with communication cable between
indoor and outdoor (U1.U2) is the outdoor unit.
• Check connection of communication line between indoor and outdoor.
• Check outdoor P.C. board(I/F) error.

Separate the cable between lines according to automatic address
setup method in “Address setup”.

In this model, only one outdoor unit is provided to one refrigerant line.
Be sure to check there is no communication connection with outdoor
unit in the other refrigerant line.

Note)
Do not set up the outdoor address manually.

In this model, only one outdoor unit is provided to one refrigerant line.
Be sure to check there is no communication connection with outdoor
unit in the other refrigerant line.

• Check the check code of outdoor follower unit.

<Convenient functions>

When pushing SW04 for 1 second or more under condition that [E28] is displayed on 7-segment display of
outdoor header unit, the fan of outdoor unit which stopped abnormally starts rotating.
If pushing SW04 and SW05 simultaneously, the fan of normal outdoor unit operates.
When pushing SW05 singly, the operation of fan is cleared.