Case 1) (case 2) – Toshiba MMU-AP0121MH User Manual

Page 110

Advertising
background image

110

Procedure 2 : Exchange of P.C. board for service

1. Exchange P.C. board with a P.C. board for service.

In this time, the jumper line (cut) setup or the (short-circuit) connecting connector setup on the previous P.C.
board should be reflected on P.C. board for service. (See the blow figures.)

2. It is necessary to set Indoor unit to be exchanged : Remote controller = 1 : 1

Based upon the system configuration, turn on power of the indoor unit with one of the following items.

1) Single (Individual) operation

Turn on power of the indoor units and proceed to Procedure 3.

2) Group operation

A) In case that power of the exchanged indoor unit only can be turned on

Turn on power of the exchanged indoor unit only and proceed to Procedure 3.

B) In case that power of the indoor units cannot be turned on individually (

Case 1)

a) Remove temporarily the group wire connected to the terminal blocks A and B of the exchanged

indoor unit.

b) After connecting the remote controller wire only to the removed terminal block, turn on power of the

indoor units and proceed to Procedure 3.

When the above methods cannot be used, follow to the two cases below.

C) In case that power of the indoor units cannot be turned on individually (

Case 2)

a) Remove all CN41 connectors of the indoor units in the same group except those of the exchanged

indoor unit.

b) Turn on power of the indoor units and proceed to Procedure 3.

After Procedure 3 operation has finished, be sure to return the temporarily removed group wire or
CN41 connector to the original connection.

(MCC-1402)

(MCC-1403)

CN41

JP1

From the left
CN112,111,110

CN34

CN041

JP001

CN030

When short-circuited plug is mounted to P.C. board before
change, re-mount the short-circuited plug as previons.

A B

A B

A B

Indoorunit

P.C. board

Indoorunit

P.C. board

Indoorunit

Service P.C. board of
the unit to be changed

Remote

controller

Group wire

A B

A B

Indoorunit

P.C. board

A B

Indoorunit

P.C. board

Indoorunit

Service P.C. board of
the unit to be changed

Remote

controller

Group wire

(Case 1)

(Case 2)

Remove the group wire of the
terminal blocks A and B of the
changed indoor unit, and then
install the remote controller only.

Remove CN41 connectors
of the indoor units other
than the units to be changed
in the same group.

CN
41