Installation of indoor unit – Toshiba MMU-AP0121MH User Manual

Page 22

Advertising
background image

22

In case of wireless type

The wireless remote controller can be operated up to a
maximum of 8 m from the infra-red receiver.

Therefore ensure that the remote controller will be
mounted and used within this stated parameter.

• To prevent malfunction do not mount or operate in a

location that is subjected to either a fluorescent lamp
or direct sunlight.

• A maximum of 6 indoor units with wireless remote

controller can be installed within the same room.

3

INSTALLATION OF INDOOR UNIT

WARNING

The installation of the air conditioning unit must be positioned in a location that can sufficiently support its weight
and give protection against adverse environmental conditions.

Failure to do so may result in unit damage and possible human injury.

Any incomplete installation may also cause possible risk of human injury.

• Unpack the package, take out the product and then place it on the floor so that the same surface directs

underneath as it is placed in the package.

• Never put the products taken out from the packing box in a

pile, or put other load on them; otherwise there is a
possibility to damage electric parts, fan parts, draining
mechanism, and etc.

If the both sides are turned over, a deformation of mounting
metal of the ceiling panel which is sold separately, etc may
be caused. Accordingly the product may be damaged and
the installation becomes impossible in some cases.

REQUIREMENT

Strictly comply to the following rules to prevent damage of the indoor units and human injury.

• Do not place heavy objects on the indoor unit. (Even when units are still packaged)

• Always carry the unit as packaged from the factory wherever possible.

If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to prevent damaging
the unit.

• To move the indoor unit, hold the hanging brackets (4 positions) only.

Do not apply force to other parts (refrigerant pipe, drain pan, foamed parts, or resin parts etc.).

• To be carried by two or more persons. Do not strap the unit in positions other than that stated.

8 m or less

2

SELECTION OF INSTALLATION PLACE

OK

NO GOOD

Dimensional view

595 to 660 Ceiling open dimension

Space required for

installation and servicing

200

525 Hanging bolt pitch

595 to 660 Ceiling open dimension

700 Panel external dimension

142

64

368.5

145.5

93

105

70

575 Unit external dimension

320.5

595 to 660 Ceiling open dimension

Check port

(

o

450)

Bottom face
of ceiling

Ceiling panel

Drain discharge port

Hanging bolt
M10 or W3/8
local arrange

Wiring connection
port

For 150 diameter
branch duct
knockout square hole

Knockout for 100 diameter
fresh air intake

Electric parts box

Ø162

For 150 diameter
branch duct knockout
square hole

4 screw holes
(For 4 mm tapping screw)

Bottom face
of ceiling

Bottom face of ceiling

Refrigerant pipe (Gas)
0151, 0181MH : Ø12.7
0071 to 0121MH : Ø9.5

Refrigerant pipe
(Liquid) Ø6.4

268

27

63

134

145.5

220.5

1000 or more

1000 or more

Obstacle

1000 or more

15 or more

15 or more

Drain-up standing-up size

Note)
As ABS is used for the drain discharge port of the main unit,
the vinyl chloride paste cannot be used.
Use the flexible hose (Band fix) included in the package.

Stand-up

627.5

or less

Ceiling

Indoor unit

Stand-up

850 or less

300 or less

55

93

105

70

139.5

190.5

21

158

214

105

177

207

575 Unit e

xter

nal dimension

105

235

235

175

149

64

29

525 Hanging bolt pitch

595 to 660 Ceiling open dimension

700 P

anel e

xter

nal dimension

256

Ø162

142

120

97.5

42

148

200

200

Check port

( 450)

Check port

( 450)

16

120

4

2.7

120

• Wired remote

controller
(RBC-AMT31E)