88

Check code name

[P26]

Check code name

G-Tr short-circuit protection error

Cause of operation

1. Outdoor unit power error

2. IPDU error/Cable connection error

3. Compressor error

4. IPDU P.C. board error

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

Is power voltage of outdoor unit normal?

Replace IPDU P.C. board.

Is compressor normal?

Is wire connector connection

on IPDU P.C. board normal?

Is smoothing condenser normal?

(1500µF, 350V)

Correct power line.

Replace compressor.

Correct connection

of wire connector.

Check capacity coming-out/

external appearance.

YES

YES

YES

YES

NO

NO

NO

NO

Check code name

[P29]

Check code name

Compressor position

detective circuit error

Cause of operation

1) Cable/connector connection error

2) Compressor error

3) IPDU P.C. board error

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

Check code name

[P31]

Check code name

Other indoor error

(Group follower unit error)

Cause of operation

Other indoor unit in the group is abnormal.

When the header unit of the group detected [E03, L03, L07, L08 error], the follower unit of the group displays [P31]
error and stops. There are no check code display and alarm record of the main remote controller.

Is not grounded?

Is not winding opened?

Are connector connection

and wiring normal?

Is not winding shorted?

(Is winding resistance 0.1 to 0.3 ?)

Check IPDU P.C. board.

Failure

Replace

Compressor error

Replace

Compressor error

Replace

Compressor error

Replace

Check and correct circuit and cables

such as cabling to compressor, etc.

YES

YES

YES

YES

NO

NO

NO

NO