Check code

Main

remote

controller

H03

H04

H06

Outdoor 7-segment display

Check code

H03

H04

H06

Auxiliary code

01: Compressor 1 side

02: Compressor 2 side

Detected

position

IPDU

I/F

I/F

Check code name

Current detection
circuit system error

Compressor 1 case
thermo operation

Low-pressure
protective operation

Status

All stop

All stop

All stop

Error detection condition

While header compressor stopped, current flowed
more than the specified current and was detected.

Compressor 1 case thermostat performed
protective operation.

Low-pressure Ps detected operation lower than
0.02MPa.

Check item (position)

• Check cabling of current detection circuit system.

• Check outdoor P.C. board (IPDU) error.

• Check compressor 1 case thermo circuit. (Connector, cable, P.C. board)

• Check full opening of service valve. (Gas and liquid side)

• Check outdoor PMV clogging. (PMV1, 2, 3)

• Check SV41 circuit leakage.

• Check miscabling/misinstallation of SV41 and SV42.

• Check valve open status of indoor PMV.

• Check 4-way valve error.

• Check refrigerant shortage.

• Check SV5 leak.

• Check SV11 circuit. (Wiring, OFF at one side only)

• Check mispiping of discharge gas/suction gas main pipe.

• Check Flow selector unit.

Check leakage of SVD valve and SVS valve.
(Check leakage of SVDD valve and SVSS.)

Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas),
wiring between FS unit and indoor unit, and connection of connectors.

Check miswiring of SVS/SVD valves.

• Check full opening of service valve.

(Discharge gas, suction gas and liquid side)

• Check outdoor PMV clogging. (PMV1, 2)

• Check SV2 circuit and SV4 circuit error.

• Check low-pressure Ps sensor error.

• Check indoor air filter clogging.

• Check valve open of indoor PMV.

• Check refrigerant pipe clogging.

• Check outdoor fan operation.

(All heating, mainly heating, part cooling operation)

• Check refrigerant shortage.

• Check clogging of circuit at auxiliary heat exchanger side.

(PMV3, SV12, check valve)

• Check 4-way valve error. (Reversal error)

• Check mispiping of discharge gas/suction gas main pipe.

• Check Flow selector unit.

Check miswiring of discharge gas/suction gas pipe to FS unit.

Check wiring between FS unit and indoor unit.

Check miswiring of SVD/SVS valves, misinstallation of coil.

Check opened status of SVS valve.