Toshiba MMU-AP0121MH User Manual

Page 57

Advertising
background image

57

MG-SW : Magnet Switch, OCR : Over-current Relay

Check item (position)

• Check TK1 sensor coming-off.

• Check characteristics of TK1 sensor resistance value.

• Check TK1, TK2, TK3, and TK4 misconnection.

• Check operation error of SV3E valve.

• Check capillary clogging of oil-equation circuit and operation error

of stop valve.

• Check refrigerant stagnation in compressor.

• Check MG-SW or OCR.

• Check TK2 sensor coming-off.

• Check characteristics of TK2 sensor resistance value.

• Check TK1, TK2, TK3, and TK4 misconnection.

• Check SV3E valve operation.

• Check capillary clogging of oil equalization circuit and check stop

valve operation.

• Check refrigerant stagnation in compressor shell.

• Check MG-SW or OCR.

• Check TK3 sensor coming-off.

• Check characteristics of TK3 sensor resistance value.

• Check TK1, TK2, TK3, and TK4 misconnection.

• Check SV3E valve operation.

• Check capillary clogging of oil-equalization circuit and check valve

operation.

• Check refrigerant stagnation in compressor shell.

• Check MG-SW or OCR.

• Check TK4 sensor coming-off.

• Check characteristics of TK4 sensor resistance value.

• Check TK1, TK2, TK3, and TK4 misconnection.

• Check SV3E valve operation.

• Check capillary clogging of oil-equalization circuit and check valve

operation.

• Check refrigerant stagnation in compressor shell.

• Check MG-SW or OCR.

• Check indoor address.

• Check the change of remote controller connection

(Group/individual) after indoor address setup.

• Check line address.

• Check display of indoor unit with priority.

Check code

Main

remote

controller

H16

L03

L04

L05

Outdoor 7-segment display

Check code

H16

L04

Auxiliary code

01: TK1 oil circuit system error

02: TK2 oil circuit system error

03: TK3 oil circuit system error

04: TK4 oil circuit system error

Detected

position

I/F

Indoor

I/F

I/F

Check code name

Oil level detective circuit system error

MG-SW error

OCR operation

Duplicated indoor center units

Duplicated outdoor line address

Duplicated indoor units with priority
(Displayed on indoor unit with priority)

Status

All stop

Corresponding
unit only stops.

All stop

All stop

Error detection condition

Temperature change of TK1 could not be
detected though compressor 1 started
the operation.

Temperature change of TK2 could not be
detected though compressor 2 started
the operation.

Temperature change of TK3 could not be
detected though compressor started the
operation.

Temperature change of TK4 could not be
detected though compressor started the
operation, or the difference from other TK
sensor changed for a constant time only
within the specified range.

There are multiple center units in a group.

Line address setup is duplicated against
the outdoor unit in different refrigerant
pipe system.

Indoor units with priority were duplicated.