Toshiba MMU-AP0121MH User Manual

Page 6

Advertising
background image

6

4. Tools

(1) Required Tools for R410A

Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.

1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

3) Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

No.

Q

R

S
T
U
V
W
X
Y
Y

Used tool

Flare tool

Copper pipe gauge for
adjusting projection
margin

Torque wrench

Gauge manifold

Charge hose

Vacuum pump adapter

Electronic balance for
refrigerant charging

Refrigerant cylinder

Leakage detector

Charging cylinder

Usage

Pipe flaring

Flaring by conventional
flare tool

Connection of flare nut

Evacuating, refrigerant
charge, run check, etc.

Vacuum evacuating

Refrigerant charge

Refrigerant charge

Gas leakage check

Refrigerant charge

Conventional air

conditioner installation

Whether new equipment
can be used with
conventional refrigerant

Yes

*(Note 1)

No

No

Yes

Yes

No

Yes

No

Whether conven-
tional equipment can
be used

*(Note 1)

*(Note 1)

No

No

No

Yes

No

No

No

(1) Vacuum pump

Use vacuum pump by
attaching vacuum pump adapter.

(2) Torque wrench

(3) Pipe cutter

(4) Reamer

(5) Pipe bender

(6) Level vial

(7) Screwdriver (+, –)

(8) Spanner or Monkey wrench

(9) Hole core drill

(10) Hexagon wrench (Opposite side 4mm)

(11) Tape measure

(12) Metal saw

Also prepare the following equipments for other installation method and run check.

(1) Clamp meter

(2) Thermometer

(3) Insulation resistance tester

(4) Electroscope

Existence of
new equipment
for R410A

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

(Note 2)

R410A

air conditioner installation

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection

margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary