Check code name

[P04]

Check code name

Actuation of

high-pressure SW

Cause of operation

1. High-pressure SW error

2. Service valve closed

3. Pd sensor error

4. Indoor/outdoor fan error

5. Indoor/outdoor PMV choke

6. Indoor/outdoor heat exchanger clogging, air short circuit

7. SV2 circuit error

8. SV4 circuit error

9. SV5 circuit error

10. Discharge line check valve malfunction

11. Refrigerant overcharge

Auxiliary code : Compressor 1 side 02: Compressor 2 side

Note) High-pressure SW is normally closed.

(B contact)

Check I/F P.C. board.

Failure

Replace

( )

Coil error, clogging,

disconnection of wiring, etc.

Connector connection,
fan IPDU, fan motor, wiring

Check and correct cabling.

Open service valve fully.

Replace defective parts.

Repair the flow selector unit.

Replace the high-pressure sensor.

Repair faulty parts.

Eliminate the interfered causes.

Repair SV2 circuit.

Correct piping.

Check parts.

Failure

Replace

A

All cooling operation

To B

All heating operation

To C

Reset power supply, and start a test
operation corresponded to the season.

Is there a cause to interfere operation

of heat exchanger of outdoor unit?

1. Heat exchanger clogging
2. Air short circuit

Is SV2 circuit normal?

B All cooling operation

Does cooling outdoor fan normally operate?

Check operation of PMV3 SV12 valve.

Is the flow selector normal?

Is circuit cabling normal?

Is service valve fully opened?

Does high-pressure SW operate?

Are parts of high-pressure SW normal?

Check mispiping of

discharge/suction gas main pipes.

Is there no crack or

coming-off of fan?

Are characteristics of

high-pressure sensor normal?

NO

NO

NO

YES

YES

NO

NO

YES

NO

NO

Abnormal

Abnormal

Abnormal

YES

YES

Normal

YES

Normal

Normal

YES

NO

YES

( )

Refrigerant overcharge, clogging,
pipe breakage, abnormal overload condition

All heating operation

Check indoor P.C. board.

Failure

Replace

Repair

faulty parts.

Replace TC2

or TCJ sensor.

Replace PMV body.

Is SV4 circuit normal?

Is SV11 circuit normal?

Are connector connection,

heat exchanger, fan, and

fan motor normal?

Are characteristics of TC2

and TCJ sensor resistance

value normal?

Is connector

connection,

coil normal?

Repair SV4 circuit.

Coil error, clogging,

disconnection of wiring, etc.

Are not indoor units of different

refrigerant circuit connected?

Is there clogging

of valve?

Is indoor

PMV normal?

Does heating indoor fan

normally operate?

Repair

faulty parts.

A

C All heating operation

Repair faulty position.

Refrigerant overcharge,
clogging,pipe breakage,
abnormal overload condition

Check and
correct the cabling.

Check with miscabling check
function of outdoor unit.

Eliminate the
interfered causes.

Is there a cause to

interfere operation of

indoor heat exchanger?

1 Air filter clogging
2 Heat exchanger clogging
3 Air short circuit

NO

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

Is 4-way valve normal?

Replace 4-way valve.

NO

NO

YES

NO

NO

NO

NO

( )

Check code name

[P05]

Check code name

Open phase, negative phase

Cause of operation

1. Power supply open phase

2. Power supply negative phase

• Check the phase power line of outdoor unit.
• Check error of outdoor I/F P.C. board.
• Check there is no looseness, etc of terminal.