Toshiba MMU-AP0121MH User Manual

Page 74

Advertising
background image

74

Check code name

[H04]

[H14]

Check code name

Compressor 1 case thermo operation

Compressor 2 case thermo operation

Cause of operation

1. Case thermo circuit error

2. I/F P.C. board error

3. Service valve closed

4. Outdoor PMV clogging

5. SV4 valve leak, Coil misinstallation

6. 4-way valve error

7. Compressor error

8. Refrigerant shortage

(Note 1)
1. Case thermo is usually closed.
2. Operation temperature of case thermo is 120˚C.

(After checking there is no slogging or pipe breakage, charge refrigerant again.)

(Note 2) Check the following items mainly.
1. Existence of abnormal sound and abnormal vibration during operation at start time
2. Abnormal overheat of case during operation or stop (Never touch with hands.)
3. Current of compressor lead during operation or starting (No rapid current change)

SV4 valve: Connector CN311, Blue

Connector CN300, 301, White

Is compressor normal? (Note 2)

Is flow selector unit normal?

Repair case thermo circuit.

Are service valves of

gas pipe and liquid pipe of
outdoor unit fully opened?

Does not refrigerant

bypass from discharge of

suction through 4-way valve?

Refrigerant shortage,

clogging, pipe breakage

Is case thermo circuit normal?

1. Connector connection
2. Wiring
3. I/F P.C. board (Note 1)

Open service valves fully.

Repair outdoor PMV.

Correct SV4, SV5, SV11

valve circuits.

Check 4-way valve.

Check piping.

Compressor error

Operation starts.

Are outdoor PMV1/2/3 normal?

1. Connector connection
2. Wiring

3. Coil

4. Valve body

5. I/F P.C. board

Are SV41 and SV42

Valve circuits normal?

1. Misinstallation installation and

connector connection of SV41
and SV42

2. Leakage from SV41, 42 circuit

NO

YES

YES

YES

YES

YES

YES

YES

NO

Check flow selector unit.

YES

NO

NO

NO

NO

NO

NO

Is not refrigerant bypassed
from discharge to suction?

Check code name

[H06]

Check code name

Low-pressure protective operation

Cause of operation

1. Service valve close

2. Ps sensor error

3. SV2, SV4 circuit error

4. Miscabling of communication between

indoor and outdoor

5. Indoor/outdoor fan and condenser error

6. Indoor/outdoor PMV clogging

7. Indoor/outdoor heat exchanger clogging

8. Refrigerant shortage

Is there clogging on whole valve?

Is outdoor fan normally

operated in heating season?

1 Pressure by pressure gauge (Check joint)
2 Pressure display on 7-segment display
3 Output voltage of I/F P.C. board

If 1 and 2, 3 are different, an error of pressure sensor error is considered.
If 2 and 3 are different, check I/F P.C. board.

Check miscabling, misinstallation and
connector connection.

(Check with miscabling check
function of outdoor unit.)

YES

YES

YES

YES

YES

YES

NO

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

YES

NO

NO

NO

NO

NO

NO

NO

Open service valves fully.

Exchange low-pressure sensor.

Correct SV2 and SV4 circuits.

Correct cabling.

Are characteristics of low-pressure sensor normal?

Is not indoor unit with different circuit connected?

Is flow selector normal?

Are SV2 and SV4 circuits normal?

Are service valves of gas and

liquid pipe of outdoor unit fully opened?

Is there no mispiping of discharge gas

and suction gas main pipes?

Does indoor fan normally

operate in cooling season?

Is outdoor PMV normal?

Is indoor PMV normal?

(A) Cooling

Is there clogging of indoor

air filter or heat exchanger?

Is there clogging of

outdoor heat exchanger?

Is connector connection

or coil normal?

YES

YES

NO

NO

Check indoor P.C. board.

Failure

Replace

YES

Correct piping.

Check flow selector.

Repair faulty parts.

Repair faulty parts.

Replace PMV body.

Repair faulty parts.

Are following items concerned

to indoor fan motor normal?

1. Connector connection
2. Condenser
3. Motor
4. Fan

Cleaning

In cooling season, go to (A), In heating season, go to (B)

Check outdoor

I/F P.C. board.

Failure

Replace

Refrigerant shortage,

clogging, pipe deformed

Refrigerant shortage or

clogging or pipe deformed

(B) Heating

Cleaning

Is indoor fan system normal?

• Fan crack
• Fan coming-off

Advertising