Drain piping work – Toshiba MMU-AP0121MH User Manual

Page 24

Advertising
background image

24

4

DRAIN PIPING WORK

REQUIREMENT

• Ensure insulating of the drain pipes and connecting parts on the indoor units.

• The drain pipe should have a downward slope of at least 1/100 and ensure

there are no swells or blockages as this will cause abnormal sounds.

• The maximum traverse length of drain pipe is 20 m. Provide support

brackets at intervals of 1.5 to 2 m where necessary to prevent movement.

• Install the combined piping as shown in the illustration.

• Do not create an air purge in the pipework,

as the water would leak from this point.

• The hard vinyl-chloride pipe cannot be connected

directly to the drain pipe connecting port of the indoor unit.
For connection with the drain pipe connecting port,
ensure that the supplied flexible hose is fitted.

• Adhesive agent cannot be used for the pipe

connecting port (hard socket) on the indoor unit.

Be sure to use the supplied hose band for fixing,
otherwise there is a risk of damage or water
leakage from the drain pipe connecting port.

CAUTION

• Install the drain piping so that the water

drains effectively.

• Apply heat insulation to prevent dew

condensation from forming.

• Incorrectly installed pipe work may result

in a water leak.

Pipe material/Insulator and size

The following materials for piping work and insulation
are to be procured locally.

Trap

Arched
shape

Support
bracket

1/100 or more
downward

Heat
insulator

1.5m to 2m

NO

GOOD

As long as possible (10cm)

VP30 or more

Downward slope
1/100 or more

VP25

VP25

VP25

(Collective pipes)

Connection of flexible hose

• Insert the soft socket of the supplied flexible hose

into the connecting port of the drain pipe.

• Align the supplied hose band to the pipe connecting

port end, and tighten.

REQUIREMENT

• Fix the soft socket with the supplied hose

band, tighten at the upper position of the
unit.

• The supplied flexible hose can bend up to

a maximum of 45°

Attached hose band Attached flexible hose

Drain pipe connecting port
(Hard socket)

VP25 vinyl chloride pipe
(Procured locally)

Adhesive agent prohibited

Soft socket

Hard socket

Socket for VP25
(Procured locally)

Riser (Trap)

90˚ Bend

max

45˚

max

45˚

OK

NO GOOD

Socket for VP25 vinyl chloride pipe
(To be local procure)

Align the attached hose band to the
end of hose, set the tightening
position upward, and then tighten it.

Indoor unit body

Drain pipe
connecting port
(Transparent)

Flexible hose
(Accessory)

VP25 vinyl chloride pipe
(To be local procure)

Pipe material

Insulator

Hard vinyl chloride pipe socket for VP25

Hard vinyl chloride pipe VP25
(Outer diameter Ø32 mm)

Foamed polyethylene foam, thickness:
10 mm or more

Connection of drain pipe

• Connect the hard socket (Procured locally) to the

hard socket side of the supplied flexible hose which
has been installed.

• Connect the drain pipes (Procured locally) in turn to

the connected hard sockets.

REQUIREMENT

• Using an adhesive agent for vinyl chloride,

connect the hard vinyl chloride pipes so that
water does not leak.

• Allow sufficient time for the adhesive to set and

harden. (Refer to the instructions of the
adhesive.)

Drain up

When it is not possible to achieve a natural downward
slope on the drain pipe, you can create a vertical lift
(Drain up) on the pipe.

• Set the height of the drain pipe within 850 mm from

the bottom surface of the ceiling.

• The drain pipe should be piped from the drain pipe

connecting port horizontally for a maximum of
300 mm and then piped vertically.

• After piping the vertical lift, ensure the pipe work is

set to a downward gradient.

Check the draining

After completion of drain piping,

Check water drains away and that no water leaks from
any of the connecting parts. At the same time check
for any abnormal sounds from the drain pump.

Ensure drainage is checked during cooling mode.

When the electric work has finished:

• Before installing the ceiling panel, pour water as

shown in the following figure, check water drains
from the drain pipe connecting port (Transparent) in
COOL mode and then check there are no water
leaks from the drain pipes.

When the electric work has not finished:

• Pull out the float switch connector (3P: Red) from

P.C. board connector (CN34: Red) of the electric
parts box. (Ensure the power is turned off.)

• Connect the single-phase 220-240V, 1N, 50Hz (or

220V, 1N, 60Hz) power to the terminal blocks R (L)
and S (N). (Never apply 220-240V to (A), (B), (U1)
and (U2).)

• Pour water referring to the next page figure.

(Amount: 1500 cc to 2000 cc)

• When the power is turned on, the drain pump motor

drives automatically. Check water is drained from
the drain pipe connecting port (Transparent), and
then check there is no water leak from the drain
pipes.

• After checking for water leaks on the drain, turn off

the power supply, and re-attach the float switch
connector to the original position (CN34) on the P.C.
board and refit the electric parts box.

Rising up

627.5mm or less

Rising up 850mm or less

300mm
or less

Indoor unit

Underneath of ceiling

220–240V, 1N

~

, 50Hz

220V 1N

~

, 60Hz

White

Black

CN34
(RED)

Black

Red

Pull out connector CN34 (Red) from P.C. board.

R(L)

S(N)

Advertising