Toshiba MMU-AP0121MH User Manual

Page 72

Advertising
background image

72

YES

YES

YES

NO

NO

NO

Are installed positions of

TE1 sensor and TL sensor correct?

Are connection of TE1 sensor connector

and TL sensor connector normal?

Are resistance characteristics of

TL sensor and TE1 sensor normal?

Check outdoor I/F P.C. board.

Defect

Replace

Correct connection of connectors.

Correct connection of connectors.

Correct installed positions of

TE1 sensor and TL sensor.

Outdoor unit temperature sensor characteristics
See TE1 sensor : Characteristics-5.
See TL sensor

: Characteristics-3.

TE1 sensor : Outdoor heat exchanger temp sensor
TL sensor : Temp sensor between liquid tanks of outdoor PMV1/2

Outdoor I/F P.C. board
TE1 sensor : CN505, Green
TL sensor : CN521, White

Check code name

[F15]

Check code name

Outdoor temp sensor miscabling

(TE1, TL)

Cause of operation

1. Misinstallation and misconnection of TE1

sensor and TL sensor

2. Resistance characteristics error of TE1

sensor and TL sensor

3. Outdoor P.C. board (I/F) error

YES

YES

YES

NO

NO

NO

Sensor error

Replace

Correct connection of connectors.
Pd sensor: CN501, Red
Ps sensor: CN500, White

Are connection of Pd sensor and

Ps sensor connectors correct?

Are output voltage characteristics of

Pd sensor and Ps sensor normal?

Are Pd/Ps output values Pd > Ps

during compressor operation?

Check outdoor I/F P.C. board.

Defect

Replace

* Value can be confirmed by 7-segment display function on outdoor I/F P.C. board.

Pd SW01/02/03=1/1/2
Ps SW01/02/03=1/2/2

1 Pressure (Check joint) by pressure gauge
2 Pressure display on 7-segment display
3 Output voltage of I/F P.C. board

If 1 and 2, 3 are different, an error of pressure sensor itself is considered.
If 2 and 3 are different, check interface P.C. board.

Check compressor.

Check code name

[F16]

Check code name

Outdoor pressure sensor miscabling

(Pd, Ps)

Cause of operation

1. High-pressure Pd sensor and low-

pressure sensor Ps are exchanged.

2. Output voltage of each sensor is zero.

Check code name

[F23]

Check code name

Ps sensor error

Cause of operation

Output voltage error of Ps sensor

YES

YES

YES

NO

NO

Is not refrigerant by

passed from discharge to

suction of 4-way valve?

Sensor error

Is connection of Ps sensor

connector correct?

Are output voltage characteristics

of Ps sensor normal?

Is there no leakage

from SV4 valve?

Replace SV4 valve.

YES

NO

NO

1 Pressure (Check joint) by pressure gauge
2 Pressure display on 7-segment display
3 Output voltage of I/F P.C. board

If 1 and 2, 3 are different, an error of pressure sensor itself is considered.
If 2 and 3 are different, check interface P.C. board.

Connector: CN500, White

Correct connection of connector.

Check 4-way valve.

Check compressor.

Check code name

[F24]

Check code name

Pd sensor error

Cause of operation

Output voltage error of Pd sensor

It is output voltage error of Pd sensor. Check disconnection of connection of connector (Pd sensor: CN501) circuit
and output voltage of sensor.
If the sensor is normal, replace outdoor I/F P.C. board.

This error is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on indoor unit P.C.
board. Replace service P.C. board.

If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write EEPROM data,
the automatic address mode is repeated. In this case, [97 error] is displayed on AI-NET central controller.

(Approx. 3 minutes)

(Approx. 1 minute)

(Power ON)

[SET DATA] is displayed

on main remote controller.

[SET DATA]
disappears.

LED (D02) 1Hz flashes

for approx. 10 seconds

on indoor unit P.C. board.

Reboot
(Reset)

(Repetition)

Check code name

[F29]

Check code name

Indoor other error

Cause of operation

Indoor P.C. board error
EEROM error