Check code

[E08]

Check code name

Duplicated indoor addresses

Cause of operation

Indoor addresses are duplicated.

Auxiliary code : Duplicated indoor address

Using a main remote controller (RBC-AMT21E), check the setup item codes (DN code) 12, 13, and 14.
When there is no address duplication, check to the following flowchart.

YES

YES

YES

NO

NO

NO

Is cable connection to

communication line normal?

Is not communication line connected

to the different outdoor unit?

Is indoor unit quantity connected

to outdoor unit correct?

Set up indoor address again.

Correct communication line.

Correct wire connection.

Check code

[E09]

Check code name

Duplicated master

remote controller

Cause of operation

Setup of master remote controller is dupli-
cated.

Check code

[E10]

Check code name

Communication error

in indoor P.C. board A’ssy

Cause of operation

Indoor P.C. board error A’ssy failure

Is there any trouble on power line?

YES

NO

Check indoor control P.C. board.

Failure

Replace

Check power voltage on line.

Eliminate noise, etc.

YES

NO

Are two remote controllers set up

as two master remote controllers?

Correct setup of remote controllers as a master:

a other. (Remote controller address connector)

Check remote controller P.C. board.

Failure

Replace

YES

NO

Are U1, U2, U3, and U4

connectors connected?

Disconnect connector connection

of U1, U2, U3, and U4.

Set up address again.

(Refer to “Address setup procedure”.)

Turn on power of

outdoor unit again.

Check code

[E12]

Check code name

Automatic address start error

Cause of operation

1. When indoor automatic address started,

other refrigerant circuit system was setting
automatic address. (Sub code : 01)

2. When outdoor automatic address started,

the indoor automatic address was being
set. (Sub-code: 02)

Auxiliary code : 01: Communication between indoor and outdoor 02: Communication between outdoor units

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Did a power failure occur?

Is there no noise source?

Is connection of CN01

connector on I/F P.C. board of

header outdoor unit correct?

Is communication line between

indoor and outdoor normal?

Is connection of CN40 connector

on indoor P.C. board correct?

Is there any connection

error of power wire?

Set up address again

after resetting power supply.

Set up address again after

resetting power supply.

Correct communication line.

Correct connection of connector.

Correct connection of connector.

Correct power wire.

Eliminate noise.

Check code

[E15]

Check code name

No corresponding indoor unit

during automatic address

Cause of operation

1. Communication line connection error

between indoor and outdoor.

2. Indoor power system error

3. Noise from surrounding devices

4. Power failure

5. Indoor P.C. board error