Check code

[E20]

Check code name

Unit connected to other line

during automatic address

Cause of operation

When starting automatic indoor address, a
device in other line is connected.

Auxiliary code : 01: Connection of outdoor in other line 02: Connection of indoor unit in other line

Separate the wire between lines according to address setup method.

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Did power failure occur?

Is there no noise source, etc?

Is there no miscabling or

disconnection on communication line

between outdoor units? ( 1)

Is the end terminal resistance

between outdoor units turned on?

(SW30 Bit 1)

Is connection of CN03 connector

on outdoor I/F P.C. board normal?

Check outdoor I/F P.C. board.

Defect

Replace

Is not main power of

outdoor unit turned off?

Check and eliminate noise, etc

Clear check code.

Turn the end terminal resistance to ON.

Turn on main power of outdoor unit.

Correct cabling of cable connector.

Correct communication line.

Check code

[E23]

Check code name

Communication sending error

between outdoor units

Cause of operation

1. Inter-unit cable connection error between

outdoor units

2. Communication connector connection error

between outdoor units, I/F P.C. board error

3. End terminal resistance setup error between

outdoor units

(

∗∗∗∗∗

1) In this model, only one outdoor unit is provided to

one refrigerant line. Be sure to check there is no
communication connection with outdoor unit in the
other refrigerant line.

YES

YES

YES

YES

NO

NO

NO

NO

Is outdoor unit setting backup?

Is main power of follower unit turned on?

Is communication line between

outdoor units connected normally?

Is communication connector (CN03)

between follower outdoor units connected?

Correct connector connection.

(Communication connector: CN03)

Check I/F P.C. board.

Clear the error, and then start operation. (

*

1)

Turn on the main power supply.

Correct connection of communication line.

Check code

[E26]

Check code name

Decrease of connected

outdoor units

Cause of operation

1. Outdoor unit backup setup

2. Outdoor power error

3. Communication line connection error between

outdoor units

4. Connector connection error for communication

5. Outdoor I/F P.C. board error

Auxiliary code : No. of outdoor units which received signals normally

(

∗∗∗∗∗

1) How to clear the error

Set SW01/SW02/SW03 on I/F P.C. board of header unit to 2/16/1, and
push SW04 for 5 seconds or more. (7-segment display: [Er.] [CL])

• In this model, only one outdoor unit is provided to one refrigerant line. Be sure to check there is no communication

connection with outdoor unit in the other refrigerant line.

Check code

[E25]

Check code name

Duplicated address setup of

terminal outdoor units

Cause of operation

Addresses are duplicated by manual setting of
outdoor address

Never set up the outdoor address manually.

Check code

[E28]

Check code name

Terminal outdoor unit error

Cause of operation

Terminal unit error

Auxiliary code : Detected outdoor unit number

SAn error occurred on the terminal unit. Confirm the check code of the terminal unit using 7-segment display on the
I/F P.C. board of the terminal unit and check it according to the diagnostic procedure for each check code.
<How to specify the terminal outdoor unit on which error occurred>
Under condition that [E28] is displayed on the 7-segment display of the header unit, when pushing SW04 for 1
second or more, the fan of the outdoor unit which stopped due to the error rotates. If pushing SW05 alone, fan
running is released.