Toshiba MMU-AP0121MH User Manual

Page 36

Advertising
background image

36

E

B

A

A zone: OFF
B zone:
Over 26˚C, below 28˚C, ULTRA LOW
C zone:
Over 28˚C, below 30˚C, LOW
D zone:
Over 30˚C, below 32˚C, MED
E zone: HIGH

D

C

32

30

28

26

20

16

(˚C)

No.

6

Outline of specifications

1. In all heating operation, the upper limit of the fan tap is set by

one with higher temperature of TC2 sensor and TCJ sensor.
• When B zone has continued for 6 minutes, the operation

shifts to C zone.

• In defrost time, the control point is set to +6°C.

Remarks

• In D and E zones, priority

is given to remote control-
ler air speed setup.

• In A “

” is displayed.

Item

Prevention of
cold air
discharge

7

Freeze
prevention
control (Low
temp. release)

1. In all cooling operation, the air conditioner operates as de-

scribed below based upon temp. detected by TC1, TC2 and
TCJ sensors.
To prevent the heat exchanger from freezing, the operation
stops.
• When “J” zone is detected for 5 minutes, the command

frequency becomes “S0” to the outdoor unit.

• In “K” zone, the timer count is interrupted, and held.
• When “

1

” zone is detected, the timer is cleared and the

operation returns to the normal operation.

• When the command frequency became S0 with continua-

tion of “J” zone, operation of the the indoor fan in LOW
mode until it reaches the “

1

” zone.

It is reset when the following conditions are satisfied.

Reset conditions
1) TC1 > 12°C and TC2 > 12°C and TCJ > 12°C
2) 30 minutes passed after stop.

2. In all cooling operation, the air conditioner operates as

described below based upon temp. detected by TC2 and TCJ
sensors.
• When “M” zone is detected for 45 minutes, the command

frequency becomes “S0” to the outdoor unit.

• In “N” zone, the timer count is interrupted and held.
• When shifting to “M” zone again, the timer count restarts

and continues.

• If “L” zone is detected, the timer is cleared and the opera-

tion returns to normal operation.

Reset conditions
1) TC1 > 12°C and TC2 > 12°C and TCJ > 12°C
2) 30 minutes passed after stop.

In a Model without TC2,
TC2 is not judged.

P2

Q2

TC2, TCJ

5°C

–2.0°C

P1

Q1

(˚C)

a

K

J

1

P2

Q2

(˚C)

L

N

M

( ) value:
When the power supply is
turned on, the Forced
thermo becomes OFF if the
temperature is less than this
indicated temperature.

P1

Q1

TC1

10°C (5°C)

0°C

TC2, TCJ

–10°C

–14°C