Check code name

[P12]

Check code name

Indoor fan motor error

Cause of operation

1. Cabling error of fan motor connector

2. Fan motor error

3. Indoor P.C. board error

Turn off power supply.

Correct connector connection.

Check indoor P.C. board (MCC-1402).

Failure

®

Replace

Is resistance value at motor side of

fan motor connector CN334 on indoor P.C. board

(MCC-1402) correct?

*

2

Is resistance value between each phase

at motor side of fan motor connector CN333 on

indoor P.C. board (MCC-1402) correct?

*

1

Is there connection error or

disconnection on connector CN333, CN334

of indoor P.C. board (MCC-1402)?

Is output of indoor fan motor position

detective signal correct?

*

3

Does fan turn without trouble

when turning it with hands?

Remove connectors CN333 and CN334

on indoor P.C. board (MCC-1402).

*

2

Check resistance value of fan motor position detective circuit.
• Is not winding 1 (Yellow lead) to 4 (Pink lead) opened/shorted?

®

Resistance should be 5 to 20k

W

*

3

Check fan motor position detective signal.

• Measure voltage with tester between CN334 1 and 5 on indoor P.C. board (MCC-1402)

under condition of CN333 and CN334 installed and power-ON.

®

Turn fan slowly with hands so that pin voltage

fluctuates

between 0 and 5V.

• Between 4 and 5: 5V

*

1

• Is not winding 1 (Red lead) to 3 (White lead), 3 (White lead) to 5 (Black lead),

5 (Black lead) to 1 (Red lead) opened/shorted?

®

Resistance value should satisfy the follows.

• Is not grounded between cabinet and 1, 3, 5?

®

Should be

10

W

or more

Replace indoor fan motor.

Replace indoor fan motor.

Replace indoor fan motor.

Replace indoor fan motor.

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

CN333

CN334

*

Detectable in model with DC fan motor
4-way Air Discharge Cassette or Concealed Duct Standard type
Under Ceiling, High Wall or Compact 4-way Air Discharge Cassette type

( )

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

Correct wiring such as cable to compressor
or connector connection.

Is power voltage normal?*

Is indoor fan normal?

s there no clogging of heat sink cooling duct?

Is screw between IPDU and heat sink loosened?

Check IPDU P.C. board.

Is wiring of IPDU normal?

Correct power line.

Check fan and fan motor.

Tighten screws.

Correct clogging.

* 380–415V ± 10%

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

Check code name

[P07]

Check code name

Heat sink overheat error

Cause of operation

1. Power voltage error

2. Outdoor fan system error

3. Heat sink installation error

4. Clogging of hear sink cooling duct

5. IPDU P.C. board error (TH sensor error)

• Check there is 380–415V voltage of

1-3 pin of CN68 on indoor P.C. board.

Check drain pipe, etc.

Does drain pump operate?

Does float SW operate?

Is wiring normal?

Is power supply to

drain pump normal?

Replace drain pump,

and check cabling.

Check indoor P.C. board.

Failure

Replace

Check indoor P.C. board.

Failure

Replace

Check and correct wiring.

Correct

connector connection.

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

Is float SW connector

(Indoor control P.C. board CN34)

connected normally?

Check code name

[P10]

Check code name

Indoor overflow error

Cause of operation

1. Float SW operation error

2. Drain pump operation error

3. Clogging of drain pipe

4. Indoor P.C. board error

Auxiliary code : Indoor address with trouble