7-5. Diagnosis Procedure for Each Check Code

Check code

[E01]

Check code name

Communication error between

indoor and remote controller

(Detected at remote controller side)

Cause of operation

1. Remote controller inter-unit cable error

2. Indoor power error

3. Indoor P.C. board error

4. Remote controller address setup error

5. Remote controller P.C. board error

Is a group control operation?

Is power of each indoor unit turned on?

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Is there no disconnection or

connector contact error on harness out

of terminal block of indoor unit?

Is the inter-unit cable of

remote controllers (A/B) normal?

Is power applied to remote controller?

AB terminals: Approx. DC18V

Is setup of two remote controllers

without main remote controller?

Correct inter-unit cable of

remote controller.

Correct connector connection

and check circuit cabling.

Check power connection status of
indoor unit. (Turn on power again.)

Check indoor P.C. board.

Defect

Replace

Change one to main/other to sub.

(Remote controller address connector)

Check remote controller P.C. board.

Defect

Replace

Check code name

Remote controller sending error

Cause of operation

Signal could not be sent to indoor unit.

Check the communication wire of the remote
controller.

* It is not displayed on 7-segment display of the central control controller.

Check code

[E02]

YES

NO

Is communication cabling between

remote controller and indoor unit correct?

Sending circuit error
inside of the remote controller

Replace remote controller.

Correct the communication cabling.

Check code

[E03]

Check code name

Communication error between

indoor and remote controller

(Detected at indoor side)

Cause of operation

No communication from remote controller and
communication adaptor

This error is detected when the indoor unit cannot receive a signal from the remote controller.
Check communication wires of the remote controllers A and B.
As communication is impossible, this check code [E03] is not displayed on the main remote controller.
It is displayed on TCC-LINK central controller.

Check code

[E04]

Check code name

Indoor/Outdoor

communication circuit error

(Detected at indoor side)

Cause of operation

1. Power of outdoor unit was firstly turned on.

2. Connection error of communication line

between indoor and outdoor

3. End terminal resistance setup error on

communication between indoor and outdoor

4. Address setup error

For details, refer to “Troubleshooting in test operation”.

Is address setup correct?

Is there no noise, etc?

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

Is connector connection from

U1/U2 terminals of indoor/outdoor

inter-unit wire normal?

Was power turned on in order
of indoor unit

outdoor unit?

Is the end terminal resistance
setup of outdoor unit normal?

Is power applied to fuse (F03)

on indoor P.C. board?

Is connection (U1/U2 terminals) of

indoor/outdoor inter-unit wire normal?

Check indoor P.C. board.

Defect

Replace

Check connection of inter-unit wire between
indoor and outdoor is correct, and then
connect communication line connector on
indoor P.C. board (CN40) to CN44 (EMG).

Correct inter-unit wire.

Turn on power again in order of

indoor unit

outdoor unit.

Correct connector connection.

Correct the end terminal resistance setup.

Set up address again.

Check noise, etc, and eliminate it if any.