Check item (position)

• Check the lock of fan motor (AC fan).
• Check cabling.

• Check full opening of outdoor service valves (Gas side, Liquid side).
• Check clogging of outdoor PMV. (PMV1,2)
• Check characteristics of TD1 sensor resistance value.
• Check refrigerant shortage.
• Check 4-way valve error.
• Check leakage of SV41 circuit.
• Check SV4 circuit. (Miswiring and misinstallation of SV41 and SV42)
• Check leakage of SV5 circuit.
• Check leakage of SV6 circuit. (Capillary clogging, valve operation error)
• Check mispiping of discharge gas/suction gas main pipe.
• Check Flow selector unit.

Check leakage of SVD valve and SVS valve.
(Check leakage of SVDD valve and SVSS.)
Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas),
wiring between FS unit and indoor unit, and connection of connectors.
Check miswiring of SVS/SVD valves.

• Check Pd pressure sensor error.
• Check full opening of outdoor service valves (Gas side, Liquid side).
• Check outdoor fan error.
• Check outdoor fan motor error.
• Check clogging of outdoor PMV. (PMV1,2)
• Check clogging of indoor/outdoor heat exchangers.
• Check short-circuiting of outdoor suction/discharge air.
• Check clogging of SV2 circuit.
• Check outdoor P.C. board (I/F) error.
• Check indoor fan system error. (Cause of air volume decrease)
• Check opening of indoor PMV.
• Check miscabling of communication line between indoor and outdoor.
• Check operation error of check valve of discharge pipe.
• Check SV4 valve circuit.
• Check SV5 valve circuit.
• Check refrigerant overcharge.
• Check mispiping of discharge gas/suction gas main pipe.
• Check circuit clogging at auxiliary heat exchanger side.

(PMV3, SV12, check valve)

• Check FS unit.

Check clogging of SVD valve and operation error.
Check wiring inside of FS unit. (SVD/SVS coil miswiring, etc.)
Check wiring between FS unit and indoor unit.
(Miswiring, Disconnection, Wiring missing)

• Check outdoor power line.
• Check outdoor P.C. board (I/F) error.

Check code

Main

remote

controller

P01

P03

P04

P05

Outdoor 7-segment display

Check code

P03

P04

P05

Auxiliary code

01: Compressor 1 side
02: Compressor 2 side

01: Power supply open phase
02: Power supply negative phase

Detected

position

Indoor

I/F

I/F

I/F

Check code name

Indoor fan motor error

Discharge temp TD1 error

Actuation of high-pressure
SW

Open phase negative
phase

Status

Corresponding
unit only stops.

All stop

All stop

All stop

Error detection condition

Discharge temp (TD1) exceeded 115°C.

High-pressure SW actuated.

• Open phase was detected when the

power turned on.

• Negative phase was detected when

the power turned on.