Error detected by TCC-LINK central control device

Check code

Display on

central control

device

C05

C06

C12

P30

Outdoor 7-segment display

Check code

(L20 is displayed.)

Auxiliary code

Differs according to error contents of the with alarm

Detected position

TCC-LINK

HA control interface

TCC-LINK

Check code name

TCC-LINK central control
device transmission error

TCC-LINK central control
device receiving error

Interface batch alarm of
HA control interface

Follower unit error of
group control

Duplicated central control
address

Status

Operation

continued.

Operation

continued.

Operation

continued.

Operation

continued.

Operation

continued.

Error detection condition

Signal is not transmit from
central control device.

Signal is not received from
central control device.

Error was input in HA control
interface

An error occurred in follower
unit of the group control.
([P30] is displayed only on the
central remote controller.)

Central control addresses
were duplicated.

Check item (position)

• Check central control device error.

• Check communication line error of central control device.

• Check setup of terminator resistor.

• Check central control device error.

• Check communication line error of central control device.

• Check setup of terminator resistor.

• Check the power of connecting destination connected device.

• Check P.C. board error of the connected device.

• Check error input.

• Check the check code of the unit with alarm.

• Check the address setup.