Check I/F P.C. board.

NO

YES

Check power voltage and line.
Correct power line.
Check external noise, etc.

Is there any trouble of

outdoor unit power supply?

Check code name

[F31]

Check code name

Outdoor EEPROM error

Cause of operation

1. Outdoor unit power error (Voltage, noise, etc.)

2. Outdoor I/F P.C. board error

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

Is power voltage of outdoor unit normal?

Is not it an abnormal overload?

Check IPDU P.C. board.

Is winding resistance

between phases of corresponding

compressor normal? (Note 1)

Does voltage drop occur

when other compressor starts?

Is connection of wiring or connection of

connector on IPDU P.C. board normal?

Correct power line.

Correct connector connection or wiring.

Correct cause of overload.

Compressor error

(Motor burning, etc.)

Note 1
* After checking the output, when connecting the compressor

lead again to the compressor terminal, check surely there is
no distortion on the Fasten receptacle terminal.
If it is loosened, caulk it with pinchers, etc and then connect
lead to the terminal firmly.

380 – 415V ± 10%

Take off lead cable of compressor.
1. Check resistance between windings:

It is normal if there are 0.7 to 0.9 .

2. Check insulation between outdoor

cabinet and terminal:
It is normal if there are 10M or more.

Check code name

[H01]

Check code name

Compressor breakdown

Cause of operation

1. Outdoor unit power line error

2. Compressor circuit system error

3. Compressor error

4. Cause of abnormal overload operation

5. IPDU P.C. board error

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

Details of compressor

power connecting section

S

C

R

Check code name

[H02]

Check code name

Compressor error (Lock)

Cause of operation

1. Outdoor unit power line error

2. Compressor circuit system error

3. Compressor error

4. Refrigerant stagnation in compressor shell

5. IPDU P.C. board error

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

Operation starts.

Is compressor normal? 2

Check IPDU P.C. board.

Is not it an abnormal overload?

Is case heater output normal?

Is power voltage of

outdoor unit normal? 1

Does voltage drop occur

when other compressor starts?

Is wiring or connector connection

on IPDU P.C. board normal?

Is there no refrigerant stagnation

in compressor shell?

Correct power line.

Correct cause of overload.

Compressor error

Correct connector connection

or wiring.

Correct refrigerant stagnation

in compressor shell.

1 380 – 415V ± 10%

2 Check the following items mainly.

1. Existence of abnormal sound and abnormal vibration during operation or starting
2. Abnormal overheat of case during operation or stop time (Never touch with hands.)
3. Current of compressor lead during operation or starting time

(No varied change of current) change

3 If OCR operates even after manual reset of OCR, check whether the wiring to the

current sensor (T02) of Comp-IPDU is correct or not.

Check case heater.

YES

NO

Does OCR of MG-SW operate?

Reset OCR manually. 3

YES

NO

Check IPDU P.C. board.

Correct connector connection or cabling.

Wiring or connector connection

on IPDU P.C. board normal?

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

Check code name

[H03]

Check code name

Current detective

circuit system error

Cause of operation

1. Cabling or connector connection error on IPDU P.C. board
2. IPDU P.C. board error