In case of installation to high ceiling

When the unit is to be installed at a height that exceeds the standard value, adjustment to the air volume is
necessary.

• For the “Setup data” in Procedure

2 , select from the “Installable ceiling height list”.

Installable ceiling height list

• Select setting by the changing of the short plugs

on the indoor P.C. board.

• Short plug position

(CN112, CN111, CN110 from the left)

7

APPLICABLE CONTROLS

Short plug position

Set

data

0000

0003

Filter sold separately

Standard filter (At shipment)

High ceiling (3)

Short

CN112 CN111 CN110

Open

CN112 CN111 CN110

In case of remote controller-less (Group control)

To set the unit to high ceiling operation, there is a method that requires the changing of the short plugs on the indoor
P.C. board. The details are shown in the below table.

This method is only to be used where a standard wired remote controller (Group control) is not used.

Upon changing the high ceiling setting

Indoor unit capacity type

Discharge direction

Standard (At shipment)

High ceiling (2)

High ceiling (3)

0071 to 0121 type

0151 type

0181 type

4-way

3-way

2-way

4-way

3-way

2-way

4-way

3-way

2-way

2.7

2.9

3.2

3.2

3.4

3.5

3.5

Setup of high ceiling

Setup data

0000

0002

0003

(Unit: m)

Change of lighting time of filter sign

Depending on the conditions of the installation, the
time period of the filter clean sign can be changed.

Follow to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [01].

• For the [Set data] in Procedure

4

, select the setup

data of filter sign lighting time from the following
table.

Increased heating effect

If it is not possible to achieve satisfactory heating due
to the installation environment or the structure of the
room. The detected temperature can be increased.
Also use a circulator, etc to circulate hot air near the
ceiling.

Follow to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [06].

• For the set data in Procedure

4

, select the setup

data of the required temperature shift value from the
table below.

Group control

In a group control, a remote controller can control up
to a maximum of 8 units.

• For cabling procedure and cables of the individual

line (Identical refrigerant line) system, refer to
“Electric work” in this Manual.

• Wiring between indoor units in a group is performed

in the following method.

Connect the indoor units by connecting the remote
controller inter-unit cables from the remote controller
terminal blocks (A, B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A, B) of the other indoor unit.
(No polarity)

• For address setup, refer to the Installation Manual

supplied with the outdoor unit.

Setup data

0000

0001

0002

0003

0004

0005

0006

Detection temp shift value

No shift

+1°C

+2°C (At shipment from factory)

+3°C

+4°C

+5°C

+6°C

Setup data

0000

0001

0002

0003

0004

Filter sign lighting time

None

150H

2500H (At shipment from factory)

5000H

10000H