Toshiba MMU-AP0121MH User Manual

Page 53

Advertising
background image

53

Check code

Main

remote

controller

E31

F01

F02

F03

F04

F05

F06

F07

F08

F10

F12

Outdoor 7-segment display

Check code

E31

F04

F05

F06

F07

F08

F12

Auxiliary code

01: IPDU1 error

02: IPDU2 error

03: IPDU1, 2 errors

04: Fan IPDU error

05: IPDU1 + Fan IPDU error

06: IPDU2 + Fan IPDU error

07: All IPDU error or communication error

between IPDU and I/F P.C. board or
outdoor I/F P.C. board error

01: TS1

02: TS2

Detected

position

I/F

Indoor unit

Indoor unit

Indoor unit

I/F

I/F

I/F

I/F

I/F

Indoor

I/F

Check code name

IPDU communication
error

Indoor TCJ sensor
error

Indoor TC2 sensor
error

Indoor TC1 sensor
error

TD1 sensor error

TD2 sensor error

TE1 sensor error

TL sensor error

TO sensor error

Indoor TA sensor
error

TS1, TS2 sensor
error

Status

All stop

Corresponding
unit only stops.

Corresponding
unit only stops.

Corresponding
unit only stops.

All stop

All stop

All stop

All stop

All stop

Corresponding
unit only stops.

All stop

Error detection condition

Communication of each IPDU (P.C. board) in
inverter box interrupted.

• Resistance value of sensor is infinite or zero.

(Open/Short)

• Resistance value of sensor is infinite or zero

(Open/Short).

• Resistance value of sensor is infinite or zero

(Open/Short).

• Resistance value of sensor is infinite or zero

(Open/Short)

• Resistance value of sensor is infinite or zero

(Open/Short)

• Resistance value of sensor is infinite or zero

(Open/Short).

• Resistance value of sensor is infinite or zero

(Open/Short).

• Resistance value of sensor is infinite or zero

(Open/Short).

• Resistance value of sensor is infinite or zero

(Open/Short).

• Resistance value of sensor is infinite or zero

(Open/Short).

Check item (position)

• Check connection of communication connector and

disconnection between IPDU and I/F P.C. board.

• Check outdoor P.C. board (I/F, IPDU, Fan IPDU) error.

• Check external noise.

• Check power supply P.C. board for fan error.

• Check connection/cabling of TCJ sensor connector.

• Check characteristics of TCJ sensor resistance value.

• Check indoor P.C. board error.

• Check connection/cabling of TC2 sensor connector.

• Check characteristics of TC2 sensor resistance value.

• Check indoor P.C. board error.

• Check connection/cabling of TC1 sensor connector.

• Check characteristics of TC1 sensor resistance value.

• Check indoor P.C. board error.

• Check connection of TD1 sensor connector.

• Check characteristics of TD1 sensor resistance value.

• Check outdoor P.C. board (I/F) error.

• Check connection of TD2 sensor connector.

• Check characteristics of TD2 sensor resistance value.

• Check outdoor P.C. board (I/F) error.

• Check connection of TE1 sensor connector.

• Check characteristics of TE1 sensor resistance value.

• Check outdoor P.C. board (I/F) error.

• Check connection of TL sensor connector.

• Check characteristics of TL sensor resistance value.

• Check outdoor P.C. board (I/F) error.

• Check connection of TO sensor connector.

• Check characteristics of TO sensor resistance value.

• Check outdoor P.C. board (I/F) error.

• Check connection/cabling of TA sensor connector.

• Check characteristics of TA sensor resistance value.

• Check indoor P.C. board error.

• Check connection of TS1 or TS2 sensor connector.

• Check characteristics of TS1, TS2 sensor resistance value.

• Check outdoor P.C. board (I/F) error.