Toshiba MMU-AP0121MH User Manual

Page 47

Advertising
background image

47

Error detected by TCC-LINK central control device

Check code

Wireless remote controller

Outdoor 7-segment display

Sensor block display

of receiving unit

Main

remote

controller

display

Auxiliary code

Operation

Timer

Ready

Flash

Check code name

Judging

device

P01

l

¤ ¤

ALT

Indoor fan motor error

Indoor

P03

P03

¤

l

¤

ALT

Discharge temp. TD1 error

I/F

P04

P04

01: Comp. 1 side

02: Comp. 2 side

¤

l

¤

ALT

High-pressure SW system operation

IPDU

P05

P05

01: Phase-missing detection

02: Phase error

¤

l

¤

ALT

Phase-missing detection /Phase error

I/F

P07

P07

01: Comp. 1 side

02: Comp. 2 side

¤

l

¤

ALT

Heat sink overheat error

IPDU, I/F

P10

P10

Detected indoor address

l

¤ ¤

ALT

Indoor overflow error

Indoor

P12

l

¤ ¤

ALT

Indoor fan motor error

Indoor

P13

P13

l

¤ ¤

ALT

Outdoor liquid back detection error

I/F

P15

P15

01: TS condition

02: TD condition

¤

l

¤

ALT

Gas leak detection

I/F

P17

P17

¤

l

¤

ALT

Discharge temp. TD2 error

I/F

P19

P19

Detected outdoor unit number

¤

l

¤

ALT

4-way valve inverse error

I/F

P20

P20

¤

l

¤

ALT

High-pressure protective operation

I/F

0

[ : IGBT short

1

[ : Fan motor position detective circuit error

3

[ : Fan motor trouble

C

[ : TH sensor temp. error (Heat sink overheat)

D

[ : TH sensor error

P22

P22

E

[ : Vdc output error

¤

l

¤

ALT

Outdoor fan IPDU error

IPDU

P26

P26

01: Comp. 1 side

02: Comp. 2 side

¤

l

¤

ALT

G-TR short protection error

IPDU

P29

P29

01: Comp. 1 side

02: Comp. 2 side

¤

l

¤

ALT

Comp position detective circuit system error

IPDU

P31

P31

¤

l

¤

ALT

Other indoor unit error
(Group terminal unit error)

Indoor

Check code

Wireless remote controller

Outdoor 7-segment display

Sensor block display

of receiving unit

Central
control

device

indication

Auxiliary code

Operation

Timer

Ready

Flash

Check code name

Judging device

C05

Sending error in TCC-LINK central control device

TCC-LINK

C06

Receiving error in TCC-LINK central control device

TCC-LINK

C12

Batch alarm of general-purpose equipment control
interface

General-purpose equipment

I/F

Differs according to error contents of unit with occurrence of alarm

Group control branching unit error

P30

(L20 is displayed.)

Duplicated central control addresses

TCC-LINK

Advertising
This manual is related to the following products: