6. APPLIED CONTROL

6-1. Setup of Selecting Function in Indoor Unit

(Be sure to Execute Setup by a Wired Remote Controller)

<Procedure> Execute the setup operation while the unit stops.

1

Push

SET

,

CL

, and

TEST

buttons simultaneously for 4 seconds or more.

The firstly displayed unit No. indicates the header indoor unit address in the group control.

In this time, the fan of the selected indoor unit is turned on.

2

Every pushing

UNIT

button, the indoor unit numbers in the group control are successively

displayed. In this time, the fan of the selected indoor unit only is turned on.

3

Specify the item code (DN) using the setup temperature

and

buttons.

4

Select the setup data using the timer time

and

buttons.

(When selecting the DN code to “33”, change the temperature indication of the unit from “°C”
to “°F” on the remote controller.)

5

Push

SET

button. (OK if display goes on.)

• To change the selected indoor unit, return to procedure

2

.

• To change the item to be set up, return to procedure

3

.

6

Pushing

TEST

button returns the status to normal stop status.

6

3
5

2

4

1

ON / OFF

FAN

TEMP.

SWING/FIX

TIME

MODE

VENT

UNIT

SET

CL

FILTER
RESET TEST

TIMER SET