78

Check code name

[H16]

Check code name

TK4 temperature detective circuit error

(Auxiliary code : 04)

Cause of operation

1. Detachment of TK4 sensor, miscabling,

characteristics error of resistance value

2. Check clogging and malfunction of

SV3E valve circuit.

3. Oil-equalization circuit error

(Check capillary clogging, strainer
clogging)

4. Refrigerant stagnation in compressor

shell

Is not TK4 sensor detached?

Is there no miscabling or misinstallation

on TK1/TK2/TK3/TK4 sensors?

Check the clogging of SV3E valve.

1 Refer to item [H07] error.

2 If OCR operates even after manual reset of OCR, check whether the wiring to the

current sensor (T02) of Comp-IPDU is correct or not.

Correct miscabling/misinstallation.

TK1: CN514
TK2: CN515
TK3: CN516
TK4: CN523

( )

YES

YES

YES

NO

NO

NO

Replace SV3E valve.

Correct installation of sensor.

Are characteristics of TK4 sensor

resistance value normal?

Check the clogging of SV3E valve.

( 1)

Error

No error

Does OCR of MG-SW operate?

YES

NO

Reset OCR manually.( 2)

Sensor error

Replace

Check I/F P.C. board

Check code name

[L03]

Check code name

Duplicated indoor header units

Cause of operation

There were two or more indoor header
units in some remote controller group
control.

1) Check the connection changing of the remote controller after the connection has been changed.
2) If the group configuration and address are normal when power has been turned on, the mode automatically shifts

to address setup mode. (Re-setup of address)

Refer to “Address setup”.

YES

YES

NO

NO

Correct the line address setup.

Correct the cable connection.

Is there duplicated line address setup?

Are communication cable connections of

[U1.U2], [U3.U4], and [U5, U6] normal?

Check outdoor I/F P.C. board.

Failure

Replace

Re-set up the address.

(Refer to “Address setup”.)

Check code name

[L04]

Check code name

Duplicated setup of outdoor line address

Cause of operation

Outdoor line addresses are duplicated.

Check code name

[L05]

Check code name

Duplicated indoor units with priority

(Displayed on indoor unit with priority)

Cause of operation

1. Two or more prior indoor units exist.

This check code is displayed on the set indoor unit when setup of indoor unit with priority is duplicated.
• Priority setup with two or more units is not available. Choose one prior unit in one refrigerant circuit system.

Check code name

[L06]

Check code name

Duplicated indoor units with priority

(Displayed on the indoor unit other than

one with priority and on the outdoor unit)

Cause of operation

Two or more indoor units with priority
are duplicated.

Auxiliary code : No. of indoor units with priority

When indoor unit with priority is duplicated, this check code is displayed on the unit other than the setup indoor unit
and outdoor unit.
• As only one indoor unit with priority is valid, change the setup.