Leaving-ON prevention control

[Function]

• This function controls the indoor units individually. It is connected with cable to the control P.C. board of the

indoor unit.

• In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code

-

is

set to the connected indoor unit.

• It is used when the start operation from outside if unnecessary but the stop operation is necessary.

• Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected.

• When inserting a card, start/stop operation from the remote controller is allowed.

• When taking out a card, the system stops if the indoor unit is operating and start/stop operation from the

remote controller is forbidden.

(1) Control items

1) Outside contact ON

: The start/stop operation from the remote controller is allowed.

(Status that card is inserted in the card switch box)

2) Outside contact OFF : If the indoor unit is operating, it is stopped forcedly.

(Start/Stop prohibited to remote controller)
(Status that card is taken out from the card switch box)

When the card switch box does not perform the above contact operation, convert it using a relay with b
contact.

(2) Operation

Handle the wired remote controller switch in the following procedure.

Use the wired remote controller switch during stop of the system.

1

Push concurrently

SET

+

CL

+

TEST

buttons for 4 seconds or more.

2

Using the setup temp

or

button, specify the item code

-

.

3

Using the timer time

or

button, set



to the setup data.

4

Push

SET

button.

5

Push

TEST

button. (The status returns to the usual stop status.)

(3) Wiring

n

Power peak-cut from indoor unit

When the relay is turned on, a forced thermostat-OFF operation starts.

1
2

1
2

3
4

3
4

5
6

5
6

CN61

T10

(YEL)

Relay (procured locally)

Indoor control P.C. board

Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.

* In the figure, the contact indicates
a status that the card is taken out.

Power supply

Outside contact (Card switch box, etc: Procured locally)

1
2

1
2

EXCT

(2P plug: RED)

CN73

Relay (procured locally)

Note) Determine the cable length between the indoor or
outdoor control P.C. board and the relay within 2m.

Relay coil signal

Indoor control P.C. board

• Wiring example