Toshiba MMU-AP0121MH User Manual

Page 54

Advertising
background image

54

(*1) All stop only in case of the header unit The follower unit continues operation.

Check code

Main

remote

controller

F13

F15

F16

F23

F24

F29

F31

H01

H02

Outdoor 7-segment display

Check code

F13

F15

F16

F23

F24

F31

H01

H02

Auxiliary code

01: Compressor 1 side

02: Compressor 2 side

01: Compressor 1 side

02: Compressor 2 side

01: Compressor 1 side

02: Compressor 2 side

Detected

position

IPDU

I/F

I/F

I/F

I/F

Indoor

I/F

IPDU

IPDU

Check code name

TH sensor error

Outdoor temp sensor
miscabling (TE1, TL)

Outdoor pressure sensor
miscabling (Pd, Ps)

Ps sensor error

Pd sensor error

Indoor other error

Outdoor EEPROM error

Compressor breakdown

Compressor error (lock)

MG-SW error

OCR operation

Status

All stop

All stop

All stop

All stop

All stop

Corresponding

unit only stops.

All stop (*1)

All stop

All stop

Error detection condition

• Resistance value of sensor is infinite or zero

(Open/Short).

During operation of compressor in HEAT mode, the
TE1 detection temp was higher than that of TL by the
specified value continued for 3 minutes or more.

High-pressure Pd sensor and low-pressure Ps sensor
were exchanged, or output voltages of both sensors
are zero.

Output voltage of Ps sensor was zero.

Output voltage of Pd sensor was zero. (Sensor Open)

Pd > 4.15MPa during stop of compressor

Indoor P.C. board did not operate normally.

Outdoor P.C. board (I/F) did not operate normally.

Inverter current detection circuit detected over-current
and stopped.

Over-current was detected several seconds after
header compressor had started.

Check item (position)

• IGBT built-in temp sensor error

Exchange IPDU P.C. board.

• Check installation of TE1 sensor and TL sensor.

• Check characteristics of TE1 and TL sensor resistance value.

• Check outdoor P.C. board (I/F) error.

• Check connection of high-pressure Pd sensor connector.

• Check connection of low-pressure Ps sensor connector.

• Check pressure sensors Pd and Ps error.

• Check outdoor P.C. board (I/F) error.

• Check compression error of compressor.

• Misconnection of Ps sensor and Pd sensor connectors

• Check connection of Ps sensor connector.

• Check Ps sensor error.

• Check compression error of compressor.

• Check 4-way valve error.

• Check outdoor P.C. board (I/F) error.

• Check SV4 circuit error.

• Check connection of Pd sensor connector.

• Check Pd sensor error.

• Check outdoor P.C. board (I/F) error.

• Check indoor P.C. board error (EEPROM error).

• Check power voltage.

• Check power noise.

• Check outdoor P.C. board (I/F) error.

• Check power voltage. (AC220–240V ± 10%).

• Check compressor error.

• Check cause of abnormal overload operation.

• Check outdoor P.C. board (IPDU) error.

• Check compressor error.

• Check power voltage. (AC380–10%, 415V +10%).

• Check cable of compressor and phase-missing.

• Check connector/terminal connection on IPDU P.C. board.

• Check conduction of case heater.

(Check activation error due to liquid stagnation in compressor.)

• Check outdoor P.C. board (IPDU) error.

• Check outdoor MG-SW or OCR.

MG-SW : Magnet Switch, OCR : Over-current Relay