Table: Function selecting item numbers (DN)

(Items necessary to perform the applied control at the local site are described.)

DN

01

02

03

04

06

0d

0E

0F

10

11

12

13

14

1E

28

2A

2E

31

32

33

5d

60

Item

Filter display delay timer

Dirty state of filter

Central control address

Specific indoor unit priority

Heating temp shift

Existence of [AUTO] mode

Follows operation mode of
the header unit

Cooling only

Type

Indoor unit capacity

Line address

Indoor unit address

Group address

Temp difference of [AUTO]
mode selection COOL

HEAT, HEAT

COOL

Automatic restart of power
failure

Selection of option/error
input (CN70)

HA terminal (CN61) select

Ventilating fan control

TA sensor selection

Temperature unit select

High ceiling selection
(Air volume selection)

Timer set
(Wired remote controller)

Description

0000 : None

0001 : 150H

0002 : 2500H

0003 : 5000H

0004 : 10000H

0000 : Standard
0001 : High degree of dirt (Half of standard time)

0001 : No.1 unit

to

0064 : No.64 unit

0099 : Unfixed

0000 : No priority

0001 : Priority

0000 : No shift

0001 : +1°C

0002 : +2°C

to

0010 : +10°C

(Up to +6 recommended)

0000 : Provided
0001 : Not provided (Automatic selection from connected outdoor unit)

0000 : Does not follow
0001 : Follows

0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])

0014: Compact 4-way Air Discharge Cassette

0000 : Unfixed

0001 to 0034

0001 : No.1 unit

to

0030 : No.30 unit

0001 : No.1 unit

to

0064 : No.64 unit

0000 : Individual

0001 : Header unit of group

0002 : Follower unit of group

0000 : 0 deg

to

0010 : 10 deg

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

0000 : None

0001 : Restart

0000 : Filter input

0001 : Alarm input (Air washer, etc.)

0002 : None

0000 : Usual

0001 : Leaving-ON prevention control

0002 : Fire alarm input

0000 : Unavailable

0001 : Available

0000 : Body TA sensor

0001 : Remote controller sensor

0000 : °C (at factory shipment)
0001 : °F

[Compact 4-way Air Discharge Cassette type]
0000 : AP007 to AP012; Below 2.7m

AP015; Below 2.9m
AP018; Below 3.2m

0002 : AP015; Below 3.2m

AP018; Below 3.4m

0003 : AP015, AP018; Below 3.5m

0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)

At shipment

0002 : 2500H

0000 : Standard

0099 : Unfixed

0000 : No priority

0002 : +2°C
(Floor type 0000: 0°C)

0001 : Not provided

0000 : Not provided

0000 : Heat pump

0014:
Compact 4-way A/D only

According to capacity type

0099 : Unfixed

0099 : Unfixed

0099 : Unfixed

0003 : 3 deg

(Ts±1.5)

0000 : None

0002 : None

0000 : Usual

(HA terminal)

0000 : Unavailable

0000 : Body TA sensor

0000 : °C

0000 : Standard