Set up All cooling mode.
Item code (DN)=OF
Cooling only operation mode=0001

Check flow selector unit.

Did set up All cooling

to All cooling indoor unit?

NO

YES

Are not two or more

central control system identical

network addresses connected?

Check the network adaptor

on the indoor P.C. board.

Correct the network address

of the central control system.

YES

NO

Check code name

[L20]

Check code name

Duplicated central

control addresses

Cause of operation

Central control addresses are duplicated.

Check code name

[L18]

Check code name

Flow selector unit system error

Cause of operation

An indoor unit which has been operated in
cooling only mode is operated in heating mode
without setup for cooling only mode.

Check code name

[L28]

Check code name

Quantity over of

connected outdoor units

Cause of operation

1. Quantity over of connected outdoor units

2. Connection error of communication line

between outdoor units

3. Outdoor I/F P.C. board error

NO

YES

YES

NO

Is No. of connected

outdoor units below 3 units?

Is communication line between

outdoor units correctly connected?

Max. 3 units are allowed for flex system.

Correct connection of communication line.

Check outdoor I/F P.C. board.

Replace IPDU P.C. board with trouble.

Correct connection of connector.

Replace communication line.

I/F P.C. board error

IPDU P.C. board error

Correct connection of connector.

Is there voltage fluctuation between

4 and 5 pins of CN600 on I/F P.C. board.

(Measurement by tester: DC0 to 5V, 5 pin GND)

Is there voltage fluctuation between

3 and 5 pins of CN600 on I/F P.C. board.

(Measurement by tester: DC0 to 5V, 5 pin GND)

Is jumper setup of outdoor I/F P.C. board correct?

(Jumpers 7, 8, 9 ON)

Is communication connector between IPDU and

I/F P.C. board connected?

Is there no disconnection of communication

line between IPDU and I/F P.C. board?

Both IPDU (No.1, No.2) and fan IPDU
did not return the communication.

YES

YES

YES

YES

YES

YES

NO

Replace fan power supply P.C. board.

NO

NO

NO

NO

NO

Auxiliary code

01

02

03

04

05

06

07

P.C. board to be replaced

IPDU1

IPDU2

IPDU1, 2

Fan IPDU

IPDU1, fan IPDU

IPDU2, fan IPDU

IPDU1, 2, fan IPDU, I/F

On the fan power supply P.C. board,

1) CN503: Between 1 and 5 pins

12V

2) CN503: Between 2 and 5 pins

7V

3) Between +5V and GND at the side of CN505: 5V

Check code name

[L29]

Check code name

IPDU quantity error

Cause of operation

1. Incorrect model setup in service for I/F P.C.

board

2. Communication error between IPDU, fan

IPDU and I/F

3. IPDU, fan IPDU, I/F P.C. board error

Auxiliary code :
01: IPDU1 error

02: IPDU2 error

03: IPDU1, 2 error

04: Fan IPDU error

05: IPDU1, fan IPDU error

06: IPDU2, fan IPDU error

07: All IPDU error or disconnection of communication line between IPDU-I/F P.C. board or outdoor I/F P.C. board error