6 operating the scroll key – Micromod MOD: 30MLTraining Manual User Manual

Page 13

Advertising
background image

Training Manual

MOD 30ML Front Face Familiarization Lab

1.4.6 Operating the Scroll key

Step Procedure

Comments

1.

Press the SCROLL key

Line 5 changes to display SP (Setpoint)

You can use the method described in section 1.4.5 - OPERATING THE RAMP KEYS to
change the value of the setpoint.

2. Press

and hold the SCROLL key

The top of the display indicates TUNE
PASSWORD
FST, SLO, and ENT indicators are flashing
Arrows appear to allow changing of the numerical
tuning password on the bottom line

3.

Press the UP key

twice to

change the bottom number to 2, and

then press ENT

The tuning password for this configuration is 2.
FIC-100 appears on Line 1
GAIN appears on Line 2
The base gain value appears on Line 6. Dual
arrows W V indicate the gain value may be
changed.

4.

Press the NXT key

RESET appears on Line 2
The base reset value appears on Line 6 (RPM =
Repeats Per Minute). Dual arrows W V indicate
the gain value may be changed.

Derivative is not configured for this
strategy.

5.

Press the NXT key

ACTION appears on Line 2
The control action, REVERSE, appears on Line 6.
Dual arrows W V indicate the action may be
changed.

Advantage: information which is useful during commissioning can be included on tuning
displays

6.

Press the NXT key

PID TYPE appears on Line 2
The configured PID type, ESPO, appears on Line
6. This represents gain on Error, Standard reset,
derivative on Process, manual reset OFF.

Advantage: information which is useful during commissioning can be included on tuning
displays

7.

Press the UP key

when you

reach the EXIT TUNING display

This returns you to the FIC-100 operating display.

1 - 7