Training Manual

Supervisory Message Lab

13.3 Instructions

Make sure the Sequence database you constructed in the Sequence Lab is loaded in ViZapp. You
should be at the top level with the DIF, IF, ST, and SE blocks visible along with the BATCH
compound.

A – ADD A TEMPERATURE CONTROLLER

Step Procedure

Comments

1. Place a new Loop Compound block in the workspace and name

it TEMP CONTROL.

2. Right-click on the new compound block and select Open

Compound.

3. On the top toolbar, click on Project / Gallery / Component

Gallery

It is important to select Component
Gallery rather than Open Component
Gallery or New Component Gallery, both
of which will try to install a new gallery
file.
If your Component Gallery appears empty,
close ViZapp. Run Restore Gallery from
the MicroMod Automation\ViZapp folder
in the Windows Start menu, then follow
the directions.
Re-open ViZapp, load your strategy and
open the Loop Compound, then access the
Component Gallery as shown at right.

4. Click on the Compounds tab in the Gallery dialog box, select the

compound ML_PID and click the Export button.

You can also double-click on the
compound to be exported to your database
instead of using the Export button.