Page 243
Advertising

Training Manual
Piecewise Linearization Lab
B - CONFIGURE THE INPUTS AND PID BLOCK
Step Procedure
Comments
4. Open the AIN, VCI and PID blocks and make the following
configuration entries:
We will leave all engineering units at 0 to
100 percent for the purposes of this lab.
AIN1
Name: FT-100
Input type: Current
AIN2
Name: LT-100
Input type: Current
Input number: 2
VCI1
Name: STM FLOW
Linearization type: Modified Square Root
VCI2
Name: LEVEL
PID
Name: LIC-100
Feedforward Compensation Type: Add
5. Make the block connections as follows:
FT-100.MODOUT to STM FLOW.MODIN
LT-100.MODOUT to LEVEL.MODIN
LEVEL.R to LIC-100.PVI
STM FLOW.R to LIC-100.FFCI
The strategy should now look something like this:
18 - 3