Sequence Lab

Enter the Transition Expressions for the steps as shown below:

Step #

Step Name

Transition Expression

2 Charge

if LevelHI then Heat

3 Heat

if Temp >= HeatSP then Cook

4 Cook

if Time >= 0:0:20.0 then Cool

5 Cool

if Temp <= CoolSP then Drain

6 Drain

if LevelLO then Idle

• After adding all the steps, the Steps tab of the SEQ Properties dialog will look like the

figure below:

Figure 12 .22.

SEQ Properties -
Steps Tab



Remember, the Transition Expression defines what makes the sequence leave the
current step and go to another. TIME is a sequence block attribute which indicates the
time in the step. There is a timer that starts as soon as you enter each step, and resets
upon transition to the next one.

• Click on OK to close the SEQ block.

10. Make connections to the Sequencer:

• Select the Multi-segment connector from the Algorithms window and then click on the

LSL (DIM) block.

• The Choose Parameter dialog of the DIM block will be displayed next.
• Select R (Result) from the list (Refer to the next figure)

12 - 16