Micromod MOD: 30MLTraining Manual User Manual
Page 48
Advertising

Training Manual
Single Loop Template Lab
3
Press NXT until “GAIN” is displayed on
line 1. Set Gain at 0.65. Then press
ENT.
0.01 to 125.0
Proportional response in a fixed gain controller.
4
Press NXT, set Reset at 30.00 then
press ENT
0.01 to 125.0
Reset in repeats per minute.
5
Press NXT until INITIAL MODE is
displayed on lines 1 and 2.
6
Set Mode to AUTO. Then press ENT
7
Press NXT until lines 2 and 6 are blank
and only the up arrow is on.
COMPOUND
will be displayed on Line 1
8
Press UP.
This completes the Control section
9
Press NXT
This takes you to the OUTPUT section of the
configuration tree.
3 - 22