Micromod MOD: 30MLTraining Manual User Manual
Page 37

Training Manual
Single Loop Template Lab
Figure 3 .11.
.
7
Press NXT to access System Scan
Groups.
Scan groups defined update intervals for
loops.
8 Press
DOWN
SYSTEM SCANGRPS
should be displayed on lines
1 and 2. See the figure above.
The arrow key will change the Scan Group
time by 50 mSec steps. Scan groups 1
through 5 are user defined intervals for loops
Leave at 0:00.100. The fastest group has the
highest priority. The lower numbered group
has a higher priority if the interval is the
same
9 Press
NXT
SCAN GROUP 2
will be displayed on lines 1 and
2.
10
Press UP to select 0:00.300
All loops included in Scan Group 2 will
execute every 300 milliseconds
11 Press
ENT
12
Press NXT until SYSTEM is displayed in
line 1, Lines 2 and 6 are blank and the
UP arrow is on.
13
Press UP
System (Tasks Exit)
14
Press NXT
SYSTEM PASWORDS
on Lines 1 and 2.
3 - 11