13 install the edited template – Micromod MOD: 30MLTraining Manual User Manual
Page 51

Training Manual
Single Loop Template Lab
3.3.13 Install the edited template
1 Press
UP
CMP LIST FIC 100
is displayed on lines 1 and 2.
2 Press
NXT
CMP LIST
is displayed on line 1; lines 2 and 6 are
blank
3 Press
UP
EDIT TEMPLATE
displayed on lines 1 and 2.
4 Press
NXT
INSTALL TEMPLATE
displayed
5
Press DOWN. Select INITWARM
INSTALL TYPE
displayed.
6
Press ENT
This compiles your configuration and loads it into
runtime memory.
You should now see the FIC-100 display. Line 2
will display the process variable and the EU
(GPM). Line 6 will display the output (50%)
7
Press the SCROLL key to see the
Setpoint at the bottom.
8
Operate your PID loop by changing the
output, setpoint and also by getting into
TUNING mode and by changing the
GAIN and RESET values.
Refer to the MOD 30ML Operation Lab 1 for more
information on operating the PID loop.
Figure 3 .25.
3 - 25