Piecewise Linearization Lab

B – CONFIGURE THE TUNE LIST BLOCK

13. Double-click on the TL (Tune List) block to open it.

14. Click on the Inputs tab, then click the Add button at the bottom

of the TL Properties menu.

The tag browser dialog box appears.

15. In the right column of the Browser, double-click LIC-100

All the attributes in the PID block appear
in the middle column.

16. While holding down the Ctrl key, select ACTION, BGAIN and

BRESET from the list in the middle column, then click the Add
button at the bottom of the dialog box.

DO NOT click “OK” yet!

This will allow adjustment of the
controller Gain, Reset, and output Action
(direct or reverse) from the front panel.




As you select the attributes they will be
highlighted.

When you click the Add button they
appear in the left window of the menu.

17. In the right window, double-click STM/FW

18. Hold down the SHIFT key and click on X1, then Y9.

All the X,Y attributes from 1 to 9 should
be highlighted

19. Click the Add button

All the X,Y attributes are added to the
right window