Training Manual

PID Loop Lab

Figure 6 .20.

VCI Properties

• Type the name and description for this block as shown above. Move the cursor to

the Linearization Type field and click on the down arrow. Select Modifies Square
Root as the type from the drop-down menu. This will compensate for errors at very
low flow measurements.

• Change the Range to 0 to 200 and Quality limits also to 0 to 200. The measured

signal (4-20mA or 1-5V) will be interpreted as 0 to 200 flow units.

• We will not change anything else in this menu. Click on the OK button to

complete the configuration of this block.

12.

Save your Document.

Figure 6 .21.

File Menu

• It is essential to save your document at frequent intervals.
• Refer to the above figure. The highlighted item is the instrument document. Click

on the Save button on the toolbar at the top to save the document. You can also
save a document by selecting File-Save from the menu bar. This saves the
instrument document.

6 - 15